Technische Zeichnung — ABB 1SAE231111R0140 — 1SAE231111R0140 — Installation Contactor

Technische Zeichnung. Representative component image; exact configuration and appearance may vary. Abbildungen dienen nur als Referenz. Das gelieferte Teil kann anders aussehen.

ABB

1SAE231111R0140 — Installation Contactor

Schütz

Teilenummer: 1SAE231111R0140

ABB 1SAE231111R0140 (ESB25-40N-01) is a four-pole installation contactor with four normally open main contacts and a 24 V AC/DC control circuit. It is rated 25 A for AC-1 duty; its AC-3 motor rating is 9 A at 230 V single-phase or 400 V three-phase. The unit measures 36 × 85 × 65 mm (W × H × D), weighs 0.245 kg and has screw terminals. It provides automatic switching without a manual operating slider and has IP20 protection.

Sie suchen ABB 1SAE231111R0140? Diese Katalogreferenz ist als „Schütz“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerABB
Teilenummer1SAE231111R0140
KategorieElektrotechnik & Steuerungen
Product Net Width36 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.245 kg
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
Rated Operational VoltageMain circuit: 220 V DC; 400 V AC
Rated Frequency (f)Control circuit: DC, 50 Hz, 60 Hz, 400 Hz; main circuit: DC, 50 Hz, 60 Hz
Rated Operational Current AC-1 (I e )(NO) 25 A
Rated Operational Current AC-3 (I e )(230 V) single-phase, NO: 9 A; (400 V) three-phase, NO: 9 A
Rated Operational Current AC-7a (I e )(NO) 25 A
Rated Operational Current AC-7b (I e )(230 V) Single Phase, NO 9 A
Rated Operational Power AC-1 (P e )(230 V) Single Phase, NO 5.8 kW
Rated Operational Power AC-3 (P e )(230 V) single-phase, NO: 1.3 kW; (400 V) three-phase, NO: 4 kW
Rated Operational Power AC-7a (P e )(230 V) Single Phase, NO 5.8 kW
Rated Operational Power AC-7b (P e )(230 V) Single Phase, NO 1.3 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )24 V AC/DC
Power Lossat Rated Operating Conditions AC-1 per Pole 2 W
Published component typeInstallation Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Ambient Air TemperatureOperation: -25 to +55 °C
Terminal TypeScrew terminals

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.