Technische Zeichnung. Representative component image; exact configuration and appearance may vary. Abbildungen dienen nur als Referenz. Das gelieferte Teil kann anders aussehen.
1SAM250000R1013 — Motor protection circuit-breaker
Elektrotechnik & SteuerungenTeilenummer: 1SAM250000R1013
ABB MS116-20, part number 1SAM250000R1013, is a three-pole manual motor starter with an adjustable 16–20 A overload setting. It provides overload, short-circuit and phase-loss protection, with a rotary manual control and trip class 10A. The device is suitable for single-phase and three-phase applications, subject to correct selection and connection.
Sie suchen ABB 1SAM250000R1013? Diese Katalogreferenz ist als „Elektrotechnik & Steuerungen“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.
Verfügbarkeit auf Anfrage
Technische Daten
| Hersteller | ABB |
|---|---|
| Teilenummer | 1SAM250000R1013 |
| Kategorie | Elektrotechnik & Steuerungen |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS116-20 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 85.4 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 10 kA at 230 V AC and 400 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 16 kA at 230 V AC and 400 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 300 A |
| Setting Range | 16–20 A |
| Rated Operational Power AC-3 (P e ) | 7.5 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 7.5 kW |
| Rated Operational Voltage | Main circuit: 690 V AC |
| Rated Operational Current (I e ) | 20 A |
| Rated Operational Current AC-3 (I e ) | 20 A |
| Rated Operational Current AC-3e (I e ) | 20 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.5 ... 2.3 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 20 A |
| Degree of Protection | Housing IP20 |
| Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Tightening Torque | Main Circuit 2 N·m |
| Wire Stripping Length | Main Circuit 10 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10A |
Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.
Fragen zum Produkt
Für dieses Teil liegen noch keine Rechercheergebnisse auf Deutsch vor. Unser Team hilft Ihnen gerne weiter.