Technische Zeichnung — ABB 1SAM350000R1014 — 1SAM350000R1014 — Motor protection circuit-breaker

Technische Zeichnung. Representative component image; exact configuration and appearance may vary. Abbildungen dienen nur als Referenz. Das gelieferte Teil kann anders aussehen.

ABB

1SAM350000R1014 — Motor protection circuit-breaker

Elektrotechnik & Steuerungen

Teilenummer: 1SAM350000R1014

ABB MS132-25, part 1SAM350000R1014, is a three-pole manual motor starter and motor protection circuit-breaker with a 20–25 A adjustable overload setting. It provides manual switching, overload and short-circuit protection, phase-loss sensitivity and a disconnect function. The device has screw terminals and a lockable rotary handle, and is rated 11 kW for three-phase AC-3 operation at 400 V.

Sie suchen ABB 1SAM350000R1014? Diese Katalogreferenz ist als „Elektrotechnik & Steuerungen“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerABB
Teilenummer1SAM350000R1014
KategorieElektrotechnik & Steuerungen
Ex Operating InstructionsATEX - Operating instructions for Manual Motor Starters MS132 for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS132-25.0
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.55 mm
Product Net Weight0.31 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 50 kA
Rated Instantaneous Short-Circuit Current Setting (I i )375 A
Setting Range20 ... 25 A
Rated Operational Power AC-3 (P e )(400 V) Three Phase 11 kW
Rated Operational Power AC-3e (P e )(400 V) Three Phase 11 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )25 A
Rated Operational Current AC-3 (I e )25 A
Rated Operational Current AC-3e (I e )25 A
Rated Operational Current DC-5 (I e )25 A
Rated Frequency (f)Main circuit: 50 / 60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 1.8 ... 2.8 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 25 A
Degree of ProtectionHousing IP20
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Extended Product TypeMS132-25
Trip Class10
Rated Service Short-Circuit Breaking Capacity at 400 V AC50 kA
Mounting on DIN RailTH35-7.5 or TH35-15
Degree of Protection - Main Circuit TerminalsIP10
Actuator TypeLockable rotary handle
Contact Position IndicationON / OFF / TRIP

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.

Fragen zum Produkt

Für dieses Teil liegen noch keine Rechercheergebnisse auf Deutsch vor. Unser Team hilft Ihnen gerne weiter.

Angebot für dieses Teil erhalten

Fühlen Sie sich zu Hause.

Wählen Sie Ihre Sprache und Ihr Lieferziel. Endgültige Preise und Versandbedingungen werden in Ihrem Angebot bestätigt.