Technische Zeichnung — ABB 1SAM451000R1017 — 1SAM451000R1017 — Motor protection circuit-breaker

Technische Zeichnung. Representative component image; exact configuration and appearance may vary. Abbildungen dienen nur als Referenz. Das gelieferte Teil kann anders aussehen.

ABB

1SAM451000R1017 — Motor protection circuit-breaker

Elektrotechnik & Steuerungen

Teilenummer: 1SAM451000R1017

ABB 1SAM451000R1017 is the MS165-65 manual motor starter and motor protection circuit-breaker. It has a 52–65 A adjustable overload setting, three poles and screw terminals. The 400 V three-phase AC-3 rating is 30 kW. Features include trip class 10 overload protection, phase-failure sensitivity, a rotary handle and separate short-circuit trip indication.

Sie suchen ABB 1SAM451000R1017? Diese Katalogreferenz ist als „Elektrotechnik & Steuerungen“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerABB
Teilenummer1SAM451000R1017
KategorieElektrotechnik & Steuerungen
Ex Operating InstructionsATEX - Operating instructions for MS165 for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS165-65
Cut-off Current CharacteristicCut-off Current Characteristic @ 400/690V -Manual Motor Starter MS165/MO165
Product Net Width55 mm
Product Net Height142.65 mm
Product Net Depth / Length122.1 mm
Product Net Weight0.98 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 50 kA
Rated Instantaneous Short-Circuit Current Setting (I i )975 A
Setting Range52–65 A
Rated Operational Power AC-3 (P e )30 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )30 kW at 400 V, three-phase
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )65 A
Rated Operational Current AC-3 (I e )65 A
Rated Operational Current AC-3e (I e )65 A
Rated Operational Current DC-5 (I e )65 A
Rated Frequency (f)50 / 60 Hz, main circuit
Operating Frequency (f sw )0 ... 415 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 8 kV
Rated Insulation Voltage (U i )1000 V
Power Lossat Rated Operating Conditions per Pole 5.14 ... 8.02 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 65 A
Degree of ProtectionIP20 housing; IP10 main circuit terminals
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 1 ... 35 mm²
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip class10

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.

Fragen zum Produkt

Für dieses Teil liegen noch keine Rechercheergebnisse auf Deutsch vor. Unser Team hilft Ihnen gerne weiter.

Angebot für dieses Teil erhalten

Fühlen Sie sich zu Hause.

Wählen Sie Ihre Sprache und Ihr Lieferziel. Endgültige Preise und Versandbedingungen werden in Ihrem Angebot bestätigt.