Schneider Electric

A9L08321 — This Acti9 iPRD8r surge arrester protects 3P installations. It allows quick replacement of damaged cartridges. The Imax maximum discharge current is 8kA .The In nominal…

Kabelführung & Energieübertragung

Teilenummer: A9L08321

A9L08321 — This Acti9 iPRD8r surge arrester protects 3P installations. It allows quick replacement of damaged cartridges. The Imax maximum discharge current is 8kA .The In nominal… — Schneider Electric reference A9L08321. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Sie suchen Schneider Electric A9L08321? Diese Katalogreferenz ist als „Kabelführung & Energieübertragung“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerSchneider Electric
TeilenummerA9L08321
KategorieKabelführung & Energieübertragung
Range of productIPRD
range of productActi9
product nameActi9 iPRD
Product or component typeSurge arrester with pluggable cartridge
Poles description3P
Remote signallingWith
Signal contacts composition1 SD (1 C/O)
[Ue] rated operational voltage400 V AC (+/- 10 %) at 50/60 Hz
Nominal discharge currentCommon mode: 2.5 kA (L/PE)
Maximum discharge currentCommon mode: 8 kA L/PE
[Uc] maximum continuous operating voltageCommon mode: 460 V L/PE
Maximum [Up] voltage protection levelCommon mode <1.6 kV type 2 L/PE Common mode <1.8 kV type 3 L/PE
[Ut] temporary overvoltage337 V L/N 5 s withstand 1455 V L/PE 200 ms safe failure mode 1455 V N/PE 200 ms safe failure mode
Signalling circuit voltage0.25 A/250 V AC 50/60 Hz
Mounting modeClip-on (DIN rail)
Height85 mm
Width54 mm
Depth69 mm
Product weight340 g
[Ipe] Ground residual current0.6 mA
Connections - terminalsTunnel type terminal (top or bottom) 2.5…25 mm² rigid Tunnel type terminal (top or bottom) 4…16 mm² flexible Tunnel type terminal (top or bottom) 4…16 mm² flexible with ferrule
Tightening torque3.5 N.m
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.

Fragen zum Produkt

Für dieses Teil liegen noch keine Rechercheergebnisse auf Deutsch vor. Unser Team hilft Ihnen gerne weiter.

Angebot für dieses Teil erhalten

Fühlen Sie sich zu Hause.

Wählen Sie Ihre Sprache und Ihr Lieferziel. Endgültige Preise und Versandbedingungen werden in Ihrem Angebot bestätigt.