C106TM080Kein Produktfoto bereitgestellt

Katalogreferenz. Verfügbarkeit, genaue Spezifikation und OEM- oder Nachmarktlieferung werden im Angebot bestätigt.

Schneider Electric

C106TM080 — This TM80D is a 4 poles 3d thermal-magnetic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 80A rating thermal-magnetic trip unit is an optimum choice for all…

Elektrotechnik & Steuerungen

Teilenummer: C106TM080

C106TM080 — This TM80D is a 4 poles 3d thermal-magnetic trip unit used on ComPacT NSX 100/160/250 circuit breakers. This 80A rating thermal-magnetic trip unit is an optimum choice for all… — Schneider Electric reference C106TM080. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Sie suchen Schneider Electric C106TM080? Diese Katalogreferenz ist als „Elektrotechnik & Steuerungen“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerSchneider Electric
TeilenummerC106TM080
KategorieElektrotechnik & Steuerungen
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Range compatibilityComPacT NSX100 ComPacT NSX160 ComPacT NSX250
Poles description4P
Protected poles description3D
Trip unit protection functionsLI
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating80 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In 15 s at 6 x Ir
Neutral protection settingsNo protection (3D)
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range640 A
Earth-leakage protectionWithout
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.