C6331M500 — This MicroLogic 1.3 M is a 3 poles 3d electronic trip unit used on ComPacT NSX 630 circuit breakers. This 500A rating electronic trip unit is an optimum choice for motor…
Sensorik & AutomatisierungTeilenummer: C6331M500
C6331M500 — This MicroLogic 1.3 M is a 3 poles 3d electronic trip unit used on ComPacT NSX 630 circuit breakers. This 500A rating electronic trip unit is an optimum choice for motor… — Schneider Electric reference C6331M500. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Sie suchen Schneider Electric C6331M500? Diese Katalogreferenz ist als „Sensorik & Automatisierung“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.
Verfügbarkeit auf Anfrage
Technische Daten
| Hersteller | Schneider Electric |
|---|---|
| Teilenummer | C6331M500 |
| Kategorie | Sensorik & Automatisierung |
| Range | ComPacT |
| Range of product | ComPacT NSX400...630 |
| Product or component type | Trip unit |
| Range compatibility | ComPacT NSX630 |
| Poles description | 3P |
| Protected poles description | 3D |
| Trip unit protection functions | SI |
| Protection type | S : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rating | 500 A at 65 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 2500 A 3000 A 3500 A 4000 A 4500 A 5000 A 5500 A 6000 A 6500 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 6500 A |
| Earth-leakage protection | Without |
| Local signalling | Flashing LED (green) for ready to operate |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |