LV430520Kein Produktfoto bereitgestellt

Katalogreferenz. Verfügbarkeit, genaue Spezifikation und OEM- oder Nachmarktlieferung werden im Angebot bestätigt.

Schneider Electric

LV430520 — This Micrologic 2.2 M is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 150A rating electronic trip unit is an optimum choice for motor…

Sensorik & Automatisierung

Teilenummer: LV430520

LV430520 — This Micrologic 2.2 M is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 150A rating electronic trip unit is an optimum choice for motor… — Schneider Electric reference LV430520. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Sie suchen Schneider Electric LV430520? Diese Katalogreferenz ist als „Sensorik & Automatisierung“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerSchneider Electric
TeilenummerLV430520
KategorieSensorik & Automatisierung
RangeComPact
Range of ProductComPact NSX100...250
Product or Component TypeTrip unit
Range CompatibilityComPact NSX160 ComPact NSX250
Number of poles3P
Protected poles description3t
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rated current150 A 149 °F (65 °C)
[Ue] rated operational voltage690 V AC 50/60 Hz
Network Frequency50/60 Hz
Complementary motor protectionPhase unbalance
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range70...150 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120 s 1.5 x Ir 5 6.5 s 6 x Ir 5 5 s 7.2 x Ir 5 240 s 1.5 x Ir 10 13.5 s 6 x Ir 10 10 s 7.2 x Ir 10 480 s 1.5 x Ir 20 26 s 6 x Ir 20 20 s 7.2 x Ir 20
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
[tsd] Short-time protection delay adjustment range0.01 s
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range2250 A
Earth-leakage protectionWithout
Local signallingFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.

Fragen zum Produkt

Für dieses Teil liegen noch keine Rechercheergebnisse auf Deutsch vor. Unser Team hilft Ihnen gerne weiter.

Angebot für dieses Teil erhalten

Fühlen Sie sich zu Hause.

Wählen Sie Ihre Sprache und Ihr Lieferziel. Endgültige Preise und Versandbedingungen werden in Ihrem Angebot bestätigt.