Komponenten-Referenzbild: Published product/series reference; confirm the exact configuration and supplied appearance.

Repräsentatives Komponentenbild, kein Foto dieser exakten Marke oder Teilenummer. Spezifikation bestätigen; das gelieferte Teil kann anders aussehen.

Schneider Electric

LV432099 — This Micrologic 5.3 E (Energy) is a 4 poles 4d electronic trip unit used on Compact NSX 630 circuit breakers. This 630A rating electronic trip unit is an optimum choice for all…

Sensorik & Automatisierung

Teilenummer: LV432099

LV432099 — This Micrologic 5.3 E (Energy) is a 4 poles 4d electronic trip unit used on Compact NSX 630 circuit breakers. This 630A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV432099. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Sie suchen Schneider Electric LV432099? Diese Katalogreferenz ist als „Sensorik & Automatisierung“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerSchneider Electric
TeilenummerLV432099
KategorieSensorik & Automatisierung
RangeComPact
Range of ProductComPact NSX400...630
Product or Component TypeTrip unit
Range CompatibilityComPact NSX630
Number of poles4P
Protected poles description3t + N/2 4t 3t 3t + OSN
Trip unit protection functionsLSI
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rated current630 A 104 °F (40 °C)
[Ue] rated operational voltage690 V AC 50/60 Hz
Network Frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range250...630 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range15…400 s 1.5 x Ir 0.35…11 s 7.2 x Ir 0.5…16 s 6 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] Short-time protection delay adjustment range0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5...11 x In
Earth-leakage protectionWithout
Neutral protection settings0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t)
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Display TypeLCD display
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.

Fragen zum Produkt

Für dieses Teil liegen noch keine Rechercheergebnisse auf Deutsch vor. Unser Team hilft Ihnen gerne weiter.

Angebot für dieses Teil erhalten

Fühlen Sie sich zu Hause.

Wählen Sie Ihre Sprache und Ihr Lieferziel. Endgültige Preise und Versandbedingungen werden in Ihrem Angebot bestätigt.