Schneider Electric

LV433963 — This Micrologic 4.3 AL is a 4 poles 4d electronic trip unit used on Compact NSX 630 circuit breakers. This 570A rating electronic trip unit is an optimum choice for all…

Kabelführung & Energieübertragung

Teilenummer: LV433963

LV433963 — This Micrologic 4.3 AL is a 4 poles 4d electronic trip unit used on Compact NSX 630 circuit breakers. This 570A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV433963. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Sie suchen Schneider Electric LV433963? Diese Katalogreferenz ist als „Kabelführung & Energieübertragung“ eingeordnet. Senden Sie die Teilenummer und Ihre Gerätedaten, damit wir Spezifikation und Verfügbarkeit prüfen und ein Angebot inklusive Versand erstellen können.

Verfügbarkeit auf Anfrage

Preis auf Anfrage

Versand inklusiveGarantie & ServiceAngebot für dieses Teil erhalten

Technische Daten

HerstellerSchneider Electric
TeilenummerLV433963
KategorieKabelführung & Energieübertragung
RangeComPact
Range of productComPact NSX400...630
Product or component typeTrip unit
Range compatibilityComPact NSX630
Number of poles4P
Protected poles description4t 3t 3t + N/2
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rated current570 A at 40 °C
[Ue] rated operational voltage440 V AC 50/60 Hz
Network frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range250...570 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
[tsd] Short-time protection delay adjustment range0.02 s
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range6900 A
Earth-leakage protectionIntegrated
Earth-leakage protection classClass A
Earth-leakage protection sensitity adjustment type IΔnAdjustable
[IΔn] earth-leakage protection sensitivity adjustment range3 A 10 A 5 A 1 A 500 mA 300 mA
Earth-leakage protection specific modeOFF using the IΔn rotary switch
Earth-leakage protection time delay adjustement type ΔtAdjustable
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Katalogangaben können fehlerhaft oder veraltet sein. Vollständige Spezifikationen und geprüfte Angaben erhalten Sie auf Anfrage. Bitte bestätigen Sie vor der Bestellung die Teilenummer und die Eignung für Ihre Maschine mit uns.