Technical illustration — ABB 1SAE231111R0122 — 1SAE231111R0122 — Installation Contactor

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAE231111R0122 — Installation Contactor

contactor

Part number: 1SAE231111R0122

ABB 1SAE231111R0122, type ESB25-22N-01, is a four-pole installation contactor with two normally open and two normally closed main contacts. It has a 24 V AC/DC control coil and a rated operational current of 25 A in AC-1 duty. The 36 mm-wide body mounts on a DIN rail and uses screw terminals. The contactor has IP20 protection and an operating ambient temperature range of -25 to +55 °C.

Looking for ABB 1SAE231111R0122? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAE231111R0122
CategoryElectrical & controls
Product Net Width36 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.245 kg
Number of Main Contacts NO2
Number of Main Contacts NC2
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
Rated Operational VoltageMain Circuit 220 V DC
Rated Frequency (f)Control Circuit 400 Hz
Rated Operational Current AC-1 (I e )25 A
Rated Operational Current AC-3 (I e )(230 V) Single Phase, NC 6 A
Rated Operational Current AC-7a (I e )(NC) 25 A
Rated Operational Current AC-7b (I e )(230 V) Single Phase, NC 6 A
Rated Operational Power AC-1 (P e )(230 V) Single Phase, NC 5.8 kW
Rated Operational Power AC-3 (P e )At 230 V single phase: NC 1.3 kW; NO 1.3 kW
Rated Operational Power AC-7a (P e )(230 V) Single Phase, NC 5.8 kW
Rated Operational Power AC-7b (P e )(230 V) Single Phase, NC 0.9 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )24 V AC/DC
Power Lossat Rated Operating Conditions AC-1 per Pole 2 W
Published component typeInstallation Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Width in Number of Modular Spacings2
MountingDIN rail
Terminal TypeScrew terminals
Degree of ProtectionIP20
Operating Ambient Temperature-25 to +55 °C

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Does ABB 1SAE231111R0122 use a 24 V AC or DC control supply?

Both. The ESB25-22N-01 version identified by 1SAE231111R0122 has a 24 V AC/DC control coil. Its control supply must not be confused with the main-contact voltage rating: the listed 400 V AC switched voltage does not mean the coil accepts 400 V.

Are all four poles of the 1SAE231111R0122 normally open?

No. This exact part has two normally open and two normally closed main contacts, designated 2NO + 2NC. It is not a four-normally-open contactor. Check the existing circuit diagram and required contact states before selecting it as a replacement.

How much DIN-rail space does the ABB ESB25-22N-01 require?

The 1SAE231111R0122 is DIN-rail mounted and has a 36 mm body width, equivalent to two modular spacings. It uses screw terminals. Allow for the wiring and enclosure layout as well as the contactor body when checking panel space.

Is the 25 A rating of 1SAE231111R0122 also its motor-load rating?

Do not treat 25 A as a universal motor rating. ABB lists 25 A for AC-1 duty, while its AC-3 power rating at 230 V single phase is 1.3 kW for both NO and NC contacts. Selection must match the load type, voltage and contact arrangement. For an equipment replacement, provide the model, serial number, existing contactor label and circuit details for verification; these ratings alone do not establish fitment.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.