Technical illustration — ABB 1SAE231111R0131 — 1SAE231111R0131 — Installation Contactor

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAE231111R0131 — Installation Contactor

contactor

Part number: 1SAE231111R0131

ABB 1SAE231111R0131, type ESB25-31N-01, is a four-pole installation contactor with a 24 V AC/DC control coil and three normally open plus one normally closed main contacts. It is rated 25 A for AC-1 and AC-7a duty. For AC-3 motor duty at 400 V three-phase, the NO-contact rating is 9 A and 4 kW. The device measures 36 mm wide by 85 mm high by 65 mm deep and weighs 0.245 kg. Load suitability depends on the utilization category, contact arrangement and operating conditions.

Looking for ABB 1SAE231111R0131? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAE231111R0131
CategoryElectrical & controls
Product Net Width36 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.245 kg
Number of Main Contacts NO3
Number of Main Contacts NC1
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
Rated Operational VoltageMain circuit: 400 V AC; 220 V DC
Rated Frequency (f)Control circuit: 50 Hz, 60 Hz, 400 Hz or DC; main circuit: 50 Hz, 60 Hz or DC
Rated Operational Current AC-1 (I e )NO: 25 A; NC: 25 A
Rated Operational Current AC-3 (I e )230 V single-phase: NO 9 A, NC 6 A; 400 V three-phase: NO 9 A
Rated Operational Current AC-7a (I e )NO: 25 A; NC: 25 A
Rated Operational Current AC-7b (I e )230 V single-phase: NO 9 A, NC 6 A; 400 V three-phase: NO 9 A
Rated Operational Power AC-1 (P e )(230 V) Single Phase, NC 5.8 kW
Rated Operational Power AC-3 (P e )230 V single-phase: NO 1.3 kW, NC 1.3 kW; 400 V three-phase: NO 4 kW
Rated Operational Power AC-7a (P e )(230 V) Single Phase, NC 5.8 kW
Rated Operational Power AC-7b (P e )(230 V) Single Phase, NC 0.9 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )24 V AC/DC
Power Lossat Rated Operating Conditions AC-1 per Pole 2 W
Published component typeInstallation Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Does ABB 1SAE231111R0131 require a 24 V AC or DC control supply?

The ESB25-31N-01 has a 24 V AC/DC control coil, so either supply type can be used at the specified control voltage. The 400 V AC main-circuit rating is not the coil voltage. The listed control frequencies include 50, 60 and 400 Hz as well as DC; a listing showing only 400 Hz is incomplete. Check the existing unit's full order code and control supply before selecting a replacement.

What does 3NO + 1NC mean on the ABB ESB25-31N-01?

This exact part has four main poles: three normally open contacts and one normally closed contact. With the coil de-energized, the three NO contacts are open and the NC contact is closed; energizing the coil reverses those states. The NC contact is a main contact, not a separate auxiliary contact. Do not treat this arrangement as four normally open poles when checking a replacement against the circuit diagram.

Is the ESB25-31N-01 rated for a 25 A motor load?

The 25 A rating applies to AC-1 and AC-7a duty, not to every motor load. For AC-3 duty, the listed NO-contact rating is 9 A and 4 kW at 400 V three-phase. At 230 V single-phase, the AC-3 current ratings are 9 A for NO contacts and 6 A for the NC contact, with 1.3 kW listed for either contact type. Select against the motor nameplate and utilization category, not just the 25 A headline. Equipment compatibility is not established by these ratings alone; provide the existing contactor code, wiring diagram and equipment model/serial number for replacement verification.

How much panel space does ABB 1SAE231111R0131 occupy?

The listed net dimensions are 36 mm wide, 85 mm high and 65 mm deep, with a net weight of 0.245 kg. Its width corresponds to two modular spacings. These are device dimensions, not a complete installation-clearance requirement; allow for wiring and any additional accessories when checking the panel layout.