Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SAE231111R0422 — Installation Contactor
contactorPart number: 1SAE231111R0422
ABB 1SAE231111R0422 is an ESB25-22N-04 four-pole installation contactor with two normally open and two normally closed main contacts. Its control circuit is rated 110–120 V AC/DC, and its AC-1 operational current is 25 A. Verify the control supply, contact arrangement and load ratings for the intended installation.
Looking for ABB 1SAE231111R0422? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAE231111R0422 |
| Category | Electrical & controls |
| Product Net Width | 36 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.24 kg |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 2 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit 400 Hz |
| Rated Operational Current AC-1 (I e ) | 25 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Current AC-7a (I e ) | (NC) 25 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-3 (P e ) | 1.3 kW at 230 V single phase, NO or NC |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 110–120 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What control voltage does ABB 1SAE231111R0422 require?
The ESB25-22N-04 has a rated control circuit voltage of 110–120 V AC/DC. Check the existing control supply before selecting it; the control voltage is separate from the load circuit voltage.
How many contacts does the ESB25-22N-04 have?
It is a four-pole installation contactor with two normally open (NO) and two normally closed (NC) main contacts. Check that this arrangement matches the circuit being controlled.
Is the 25 A rating suitable for every load on this contactor?
No. ABB specifies 25 A for AC-1 duty; the appropriate rating depends on the load and utilization category. For AC-3 at 230 V single phase, ABB lists 1.3 kW for both NO and NC contacts. Check the actual load and full ratings before selection.
Can this contactor replace the one in my equipment?
Compatibility cannot be established from the part number alone. Compare the existing contactor’s part number, coil supply, contact arrangement and load ratings; provide the equipment model and serial number for verification.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.