contactorPart number: 1SAE231111R0613
ABB ESB25-13N-06 (1SAE231111R0613) is a four-pole installation contactor with one normally open and three normally closed main contacts. It has a 230–240 V AC/DC control circuit and a 25 A AC-1 rating. Its modular width is two spacings, and it includes integrated overvoltage protection.
Looking for ABB 1SAE231111R0613? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAE231111R0613 |
| Category | Electrical & controls |
| Product Net Width | 36 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.235 kg |
| Number of Main Contacts NO | 1 |
| Number of Main Contacts NC | 3 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4 |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit 400 Hz |
| Rated Operational Current AC-1 (I e ) | 25 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Current AC-7a (I e ) | (NC) 25 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230–240 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Width in modular spacings | 2 |
| Built-in depth | 58 mm |
| Degree of protection | IP20 |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What contact arrangement does ABB 1SAE231111R0613 have?
The ESB25-13N-06 has four main contacts: one normally open and three normally closed. Check the contact arrangement as well as the coil voltage when selecting a replacement.
What control voltage does the ESB25-13N-06 require?
Its rated control voltage is 230–240 V AC/DC. Verify the available control supply and the existing device identification before ordering a replacement.
Is the 25 A rating suitable for every load?
No. The 25 A rating is listed for utilization category AC-1; suitability depends on the load and operating conditions. Check the appropriate rating for the intended load before selection.
How much panel space does this contactor occupy?
The contactor is two modular spacings wide. The listed built-in depth is 58 mm; allow for the complete installation and wiring when checking enclosure space.