Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SAE351111R0440 — Installation Contactor
contactorPart number: 1SAE351111R0440
ABB 1SAE351111R0440, type ESB63-40N-04, is a four-pole installation contactor with four normally open main contacts and a 110 V AC/DC control circuit. It is rated 63 A for AC-1 and mounts on a DIN rail. Check the utilisation category and load ratings when selecting the contactor.
Looking for ABB 1SAE351111R0440? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAE351111R0440 |
| Category | Electrical & controls |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.405 kg |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main circuit: 220 V DC; 400 V AC |
| Rated Frequency (f) | Control circuit: 50 Hz, 60 Hz, 400 Hz or DC; main circuit: 50 Hz, 60 Hz or DC |
| Rated Operational Current AC-1 (I e ) | (NO) 63 A |
| Rated Operational Current AC-3 (I e ) | (230 V) single-phase, NO: 30 A; (400 V) three-phase, NO: 30 A |
| Rated Operational Current AC-7a (I e ) | (NO) 63 A |
| Rated Operational Current AC-7b (I e ) | (230 V) single-phase, NO: 30 A; (400 V) three-phase, NO: 30 A |
| Rated Operational Power AC-1 (P e ) | (230 V) single-phase, NO: 14.5 kW; (400 V) three-phase, NO: 43.6 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) single-phase, NO: 5 kW; (400 V) three-phase, NO: 15 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) single-phase, NO: 14.5 kW; (400 V) three-phase, NO: 43.6 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) single-phase, NO: 5 kW; (400 V) three-phase, NO: 15 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 240 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 110 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 4.5 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting | 35 mm DIN rail |
| Degree of Protection | IP20 |
| Ambient Operating Temperature | -25 to +55 °C |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What control voltage does ABB 1SAE351111R0440 require?
The ESB63-40N-04 has a rated control circuit voltage of 110 V AC/DC. Verify that the available control supply matches the coil before selecting it.
How many main contacts does the ESB63-40N-04 have?
It is a four-pole contactor with four normally open main contacts and no normally closed main contacts.
Can the 63 A contactor be used for a motor load?
Its ratings depend on the utilisation category: AC-1 is 63 A, while the listed AC-3 rating is 30 A at 230 V single-phase or 400 V three-phase. The listed AC-3 powers are 5 kW and 15 kW respectively. Check the motor and operating conditions before selection.
How much panel space does 1SAE351111R0440 need and how is it mounted?
The contactor is designed for DIN-rail mounting. Its net dimensions are 54 mm wide, 85 mm high and 65 mm deep; check the available enclosure space before ordering.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.