Technical illustration — ABB 1SAE661111R0140 — 1SAE661111R0140 — Installation Contactors

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAE661111R0140 — Installation Contactors

contactor

Part number: 1SAE661111R0140

ABB 1SAE661111R0140 (ESB100-40N-01) is a four-pole installation contactor with four normally open main contacts and a 24 V AC/DC control coil. It is rated 100 A for AC-1 and AC-7a use and is designed for switching single-phase and three-phase loads.

Looking for ABB 1SAE661111R0140? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAE661111R0140
CategoryElectrical & controls
Product Net Width108 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.81 kg
Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles4P
Rated Operational VoltageMain circuit: 400 V AC; 220 V DC
Rated Frequency (f)Control circuit: DC, 50, 60 or 400 Hz; main circuit: DC, 50 or 60 Hz
Rated Operational Current AC-1 (I e )(NO) 100 A
Rated Operational Current AC-7a (I e )(NO) 100 A
Rated Operational Power AC-1 (P e )23 kW at 230 V single-phase; 69.3 kW at 400 V three-phase
Rated Operational Power AC-7a (P e )(230 V) Single Phase, NO 23 kW
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-1) 150 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )24 V AC/DC
Power Lossat Rated Operating Conditions per Pole 4.2 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Connecting Capacity Main CircuitFlexible with Ferrule 1x 10 ... 35 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1x 1 ... 2.5 mm²
Wire Stripping LengthControl Circuit 7 mm
Degree of ProtectionIP20
Tightening TorqueControl Circuit 0.9 N·m
Terminal TypeScrew Terminals
Published component typeInstallation Contactors
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Ambient Air TemperatureOperation: -25 to +55 °C; storage: -40 to +80 °C

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What control voltage does ABB 1SAE661111R0140 require?

The ESB100-40N-01 has a 24 V AC/DC control coil. Do not confuse the coil voltage with the voltage switched by the main contacts; verify the control supply before ordering.

How many contacts does the ESB100-40N-01 have?

It is a four-pole installation contactor with four normally open main contacts. Verify the contact arrangement and control voltage against the existing device before selecting a replacement.

Is the 100 A rating suitable for every type of load?

No. The 100 A rating applies to normally open contacts in the AC-1 and AC-7a utilization categories at an ambient temperature up to 55 °C. ABB does not list an AC-3 motor rating for ESB100..N in its catalog. Check the load category and application before selection.

What are the dimensions of the ABB ESB100-40N-01 contactor?

The listed net dimensions are 108 mm wide, 85 mm high and 65 mm deep, with a net weight of 0.81 kg. Check available panel space and installation requirements before ordering.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.