Technical illustration — ABB 1SAL102636R9901 — 1SAL102636R9901 — Mini Contactor

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAL102636R9901 — Mini Contactor

contactor

Part number: 1SAL102636R9901

ABB 1SAL102636R9901 is the MC1A301ATW three-pole mini contactor, with three normally open main contacts, one normally closed auxiliary contact and screw terminals. Its AC control coil is rated 415–440 V at 50 Hz or 480 V at 60 Hz. At 400 V, its AC-3 rating is 9 A and 4 kW for a three-phase load. It is suitable for wall or rail mounting.

Looking for ABB 1SAL102636R9901? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAL102636R9901
CategoryElectrical & controls
Product Net Width45 mm
Product Net Depth / Length56 mm
Product Net Height48 mm
Product Net Weight0.17 kg
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC1
Number of Poles3P
Rated Operational VoltageAuxiliary Circuit 690 V AC
Rated Frequency (f)Auxiliary Circuit 50 Hz
Conventional Free-air Thermal Current (I th )Auxiliary Circuit 10 A
Rated Operational Current AC-1 (I e )(690 V) 55 °C 20 A
Rated Operational Current AC-3 (I e )9 A at 230 V or 400 V, 55 °C; 8 A at 500 V, 55 °C; 5 A at 690 V, NO, 55 °C
Rated Operational Current AC-15 (I e )(240 V) 6 A
Rated Operational Current DC-13 (I e )(24 V) 5 A
Rated Operational Power AC-3 (P e )Three phase: 2.2 kW at 230 V; 4 kW at 400 V or 500 V; 4 kW at 690 V, NO
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )750 V
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Minimum Switching CapacityAuxiliary Circuit 17 V
Coil Operating Limits(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )415–440 V AC at 50 Hz; 480 V AC at 60 Hz
Power Lossat Rated Operating Conditions AC-1 per Pole 0.7 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Published component typeMini Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Terminal TypeScrew terminals
MountingWall or rail mounting
Operating Ambient Temperature−40 to +70 °C

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What coil voltage does the ABB 1SAL102636R9901 mini contactor require?

The MC1A301ATW coil is rated for 415–440 V AC at 50 Hz or 480 V AC at 60 Hz. Check the control supply separately from the main circuit voltage before selecting a replacement.

What are the main and auxiliary contacts on the MC1A301ATW?

It has three normally open main contacts and one normally closed auxiliary contact. The auxiliary contact is separate from the three main poles.

What motor load rating does this ABB mini contactor have at 400 V?

ABB lists 4 kW for a three-phase load at 400 V in AC-3, with an AC-3 operational current of 9 A at 55 °C. Selection also depends on the actual load and operating conditions; these ratings are not a blanket compatibility guarantee.

How is the MC1A301ATW mounted and connected?

The contactor has screw terminals and is suitable for wall or rail mounting. Its dimensions are 45 mm wide, 56 mm deep and 48 mm high; check the available space and mounting arrangement before ordering.

Can 1SAL102636R9901 replace the contactor in my equipment?

Compatibility depends on the existing part and the equipment's electrical requirements. Compare the complete part number, coil voltage, contact arrangement, load ratings and mounting. If uncertain, provide the equipment model and serial number and the existing contactor's nameplate details for verification.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.