1SAM250000R1003 — Motor protection circuit-breaker
Electrical & controlsPart number: 1SAM250000R1003
ABB MS116-0.4 (1SAM250000R1003) is a three-pole manual motor starter with an adjustable 0.25–0.40 A overload setting. It provides overload and short-circuit protection, phase-loss sensitivity and manual motor switching. Its rated AC-3 operational power is 0.09 kW at 400 V.
Looking for ABB 1SAM250000R1003? This catalogue reference is listed under Electrical & controls. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAM250000R1003 |
| Category | Electrical & controls |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS116-0.40 valid for productiondate from week 34/2014 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116 |
| Product Net Width | 45 mm |
| Product Net Height | 90 mm |
| Product Net Depth / Length | 85.6 mm |
| Product Net Weight | 0.225 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 50 kA at 230 V AC; 50 kA at 400 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 100 kA at 230 V AC; 100 kA at 400 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 5 A |
| Setting Range | 0.25–0.40 A |
| Rated Operational Power AC-3 (P e ) | 0.09 kW at 400 V |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 0.09 kW |
| Rated Operational Voltage | 690 V AC, main circuit |
| Rated Operational Current (I e ) | 0.4 A |
| Rated Operational Current AC-3 (I e ) | 0.4 A |
| Rated Operational Current AC-3e (I e ) | 0.4 A |
| Rated Frequency (f) | 50/60 Hz, main circuit |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV, main circuit |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 0.6 ... 1.7 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 0.4 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10A |
| Mounting | 35 mm DIN rail TH35-7.5 or TH35-15 |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What motor current range does the ABB MS116-0.4 cover?
Its adjustable overload setting range is 0.25–0.40 A. The motor’s rated current must fall within that range; also verify the voltage and protection requirements before selection.
What protection does 1SAM250000R1003 provide?
The MS116-0.4 provides thermal overload and electromagnetic short-circuit protection, with phase-loss sensitivity. It also allows manual on/off switching and has a disconnect function.
What is its short-circuit breaking capacity at 400 V AC?
ABB’s MS116 data sheet lists a rated service breaking capacity (Ics) of 50 kA and ultimate breaking capacity (Icu) of 100 kA at 400 V AC for the MS116-0.4. Check the applicable rating and installation conditions for the circuit.
Can this motor protection breaker be used with a single-phase motor?
ABB lists the MS116 for single- and three-phase applications. Suitability depends on motor current, voltage, protection requirements and the correct connection arrangement; consult the ABB documentation and a qualified electrical professional.