1SAM250000R1009 — Motor protection circuit-breaker

Electrical & controls

Part number: 1SAM250000R1009

ABB 1SAM250000R1009 is the MS116-6.3 three-pole manual motor starter and motor protection circuit-breaker. It has an adjustable 4.0–6.3 A thermal overload setting, trip class 10A and a 2.2 kW AC-3 rating at 400 V. It provides manual motor switching and protection against overload, short circuit and phase failure. Suitability depends on motor and circuit ratings.

Looking for ABB 1SAM250000R1009? This catalogue reference is listed under Electrical & controls. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAM250000R1009
CategoryElectrical & controls
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS116-6.3
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length85.6 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )50 kA at 230 V AC and 400 V AC; 6 kA at 440 V AC and 500 V AC; 2 kA at 690 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )75 kA at 230 V AC and 400 V AC; 18 kA at 440 V AC; 15 kA at 500 V AC; 3 kA at 690 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )78.8 A
Setting Range4.0–6.3 A
Rated Operational Power AC-3 (P e )2.2 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 2.2 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )6.3 A
Rated Operational Current AC-3 (I e )6.3 A
Rated Operational Current AC-3e (I e )6.3 A
Rated Frequency (f)50/60 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 6.3 A
Degree of ProtectionHousing IP20
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10A
Mounting on DIN RailTH35-7.5 or TH35-15, 35 mm DIN rail

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What is the overload setting range for ABB 1SAM250000R1009?

The MS116-6.3 has an adjustable thermal overload setting range of 4.0–6.3 A and a rated operational current of 6.3 A. Select it only when the motor current is within that range; check the motor nameplate and installation requirements.

What motor power is the MS116-6.3 rated for at 400 V?

ABB lists 2.2 kW at 400 V AC for AC-3 duty. The power rating alone does not establish suitability: check the motor current, supply and circuit protection requirements.

What are its short-circuit breaking ratings at 400 V AC?

At 400 V AC, the MS116-6.3 is rated for 50 kA service breaking capacity (Ics) and 75 kA ultimate breaking capacity (Icu). Ratings depend on voltage and standard; verify prospective fault current and any backup protection requirements for the installation.

Can the MS116-6.3 be used with a single-phase motor?

ABB identifies the MS116 as suitable for single-phase as well as three-phase applications. The motor current must fall within the 4.0–6.3 A setting range; verify the circuit design and ABB wiring information before selection.