1SAM340000R1004 — Power circuit-breaker for trafo/generator/installation protection
Electrical & controlsPart number: 1SAM340000R1004
ABB MS132-0.63T (1SAM340000R1004) is a three-pole circuit breaker designed for primary-side control transformer protection against overload and short circuit. It has a 0.40–0.63 A adjustable overload range, screw terminals and a rotary handle for manual disconnection. The rated service breaking capacity is 100 kA at 400 V AC.
Looking for ABB 1SAM340000R1004? This catalogue reference is listed under Electrical & controls. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAM340000R1004 |
| Category | Electrical & controls |
| Time-Current Characteristic Curve | Tripping characteristic - Circuit Breaker for Transformer Protection MS132-0.63T |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V - Circuit Breaker for Transformer Protection MS132-T / MS132-KT |
| Product Net Width | 45 mm |
| Product Net Height | 90 mm |
| Product Net Depth / Length | 86.75 mm |
| Product Net Weight | 0.215 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 100 kA at 230 V AC and 400 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 100 kA at 400 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 12.6 A |
| Setting Range | 0.40–0.63 A |
| Rated Operational Voltage | Main circuit: 690 V AC |
| Rated Operational Current (I e ) | 0.63 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz |
| Operating Frequency (f sw ) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 0.6 ... 1.5 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 0.63 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Mounting on DIN Rail | TH35-7.5 and TH35-15, 35 mm rail |
| Minimum Mounting Distance | Electrical Conductive Board, Vertical 75 mm |
| Short-Circuit Current Rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA |
| Published component type | Power circuit-breaker for trafo/generator/installation protection |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10 |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What does ABB 1SAM340000R1004 protect?
The MS132-0.63T is designed for primary-side protection of control transformers against overload and short circuit. It also provides manual disconnection. Confirm the transformer nameplate and system requirements before selection.
What current range does the MS132-0.63T cover?
Its adjustable overload setting range is 0.40–0.63 A, and its rated operational current is 0.63 A. The transformer’s actual nominal current must fall within the setting range.
What is the breaking capacity at 400 V AC?
ABB lists both the rated service breaking capacity (Ics) and ultimate breaking capacity (Icu) as 100 kA at 400 V AC. The required capacity depends on the available fault current and application.
Does the 1SAM340000R1004 use screw terminals and DIN-rail mounting?
Yes. This MS132-0.63T version has screw terminals and supports TH35-7.5 and TH35-15 mounting rails. Verify the existing device and available space before ordering.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.