Technical illustration — ABB 1SAM340000R1006 — 1SAM340000R1006 — Power circuit-breaker for trafo/generator/installation protection

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAM340000R1006 — Power circuit-breaker for trafo/generator/installation protection

Electrical & controls

Part number: 1SAM340000R1006

ABB MS132-1.6T (1SAM340000R1006) is a three-pole circuit breaker designed for primary-side control transformer protection. It provides overload and short-circuit protection, with an adjustable 1.0–1.6 A overload setting and a fixed 32 A instantaneous short-circuit setting. The breaker has screw terminals, a rotary handle and a disconnect function.

Looking for ABB 1SAM340000R1006? This catalogue reference is listed under Electrical & controls. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAM340000R1006
CategoryElectrical & controls
Time-Current Characteristic CurveTripping characteristic - Circuit Breaker for Transformer Protection MS132-1.6T
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V - Circuit Breaker for Transformer Protection MS132-T / MS132-KT
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )100 kA at 400 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )100 kA at 400 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )32 A
Setting Range1.0–1.6 A
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )1.6 A
Rated Frequency (f)Main circuit: 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.6 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 1.6 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-7.5 or TH35-15, IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mm
Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Published component typePower circuit-breaker for trafo/generator/installation protection
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10
Ambient Operating TemperatureOpen: −25 to +70 °C; temperature compensated: −25 to +60 °C

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What is ABB 1SAM340000R1006 designed to protect?

It is the MS132-1.6T circuit breaker, designed for primary-side control transformer protection against overload and short circuit. Suitability depends on the transformer and circuit ratings.

What is the overload setting range for MS132-1.6T?

The adjustable overload setting range is 1.0–1.6 A. ABB advises choosing a breaker whose range includes the actual nominal current; other circuit requirements must also be checked.

What are the short-circuit trip setting and breaking capacity?

The instantaneous short-circuit setting is 32 A. ABB lists both service and ultimate short-circuit breaking capacity as 100 kA at 400 V AC; verify the applicable circuit conditions.

Does the MS132-1.6T have screw terminals and DIN-rail mounting?

Yes. This T version has screw terminals and mounts on TH35-7.5 or TH35-15 DIN rail. Its three-pole construction and circuit ratings should be checked against the intended installation.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.