Technical illustration — ABB 1SAM340000R1014 — 1SAM340000R1014 — Power circuit-breaker for trafo/generator/installation protection

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAM340000R1014 — Power circuit-breaker for trafo/generator/installation protection

Electrical & controls

Part number: 1SAM340000R1014

ABB MS132-25T (1SAM340000R1014) is a three-pole circuit breaker designed for primary-side protection of control transformers. It provides overload and short-circuit protection, a 20–25 A adjustable overload setting, screw terminals and a lockable rotary handle with ON/OFF/TRIP indication.

Looking for ABB 1SAM340000R1014? This catalogue reference is listed under Electrical & controls. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAM340000R1014
CategoryElectrical & controls
Time-Current Characteristic CurveTripping characteristic - Circuit Breaker for Transformer Protection MS132-25T
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V - Circuit Breaker for Transformer Protection MS132-T / MS132-KT
Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.05 mm
Product Net Weight0.31 kg
Rated Service Short-Circuit Breaking Capacity (I cs )50 kA at 400 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )50 kA at 400 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )500 A
Setting Range20–25 A
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )25 A
Rated Frequency (f)Main circuit: 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 1.2 ... 1.9 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 25 A
Degree of ProtectionHousing: IP20; main circuit terminals: IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Tightening TorqueMain Circuit 2 N·m
Wire Stripping LengthMain Circuit 10 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 or TH35-7.5, 35 mm rail according to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mm
Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA
Published component typePower circuit-breaker for trafo/generator/installation protection
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What is ABB 1SAM340000R1014 designed to protect?

This is the MS132-25T circuit breaker, designed for primary-side protection of control transformers against overload and short circuits. The breaker also provides a manual disconnect function.

What are the overload and short-circuit settings of the MS132-25T?

The overload setting is adjustable from 20 to 25 A. The instantaneous short-circuit setting is fixed at 500 A to accommodate transformer inrush; it is not an adjustable 20–25 A setting.

What is the breaking capacity of the MS132-25T at 400 V AC?

ABB lists both service breaking capacity Ics and ultimate breaking capacity Icu as 50 kA at 400 V AC. Breaking capacity varies with voltage; suitability also depends on the installation’s prospective fault current and protection coordination.

How can I check whether the MS132-25T suits my transformer?

Check that the transformer’s rated primary current is within the 20–25 A setting range and confirm voltage, inrush and fault-current requirements. Provide the equipment model and serial number, transformer nameplate and existing breaker reference for verification; fitment is not established by part number alone.