Catalogue reference. Availability, exact specification and OEM or aftermarket supply are confirmed in your quotation.
1SAM350000R1015 — Motor protection circuit-breaker
Electrical & controlsPart number: 1SAM350000R1015
ABB 1SAM350000R1015 is the MS132-32 manual motor starter and motor protection circuit-breaker. This three-pole, screw-terminal device has an adjustable 25–32 A overload range and a 32 A rated operational current. It combines manual switching with thermal overload and magnetic short-circuit protection and is sensitive to phase loss. Its published AC-3 rating is 15 kW at 400 V, three-phase.
Looking for ABB 1SAM350000R1015? This catalogue reference is listed under Electrical & controls. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAM350000R1015 |
| Category | Electrical & controls |
| Ex Operating Instructions | ATEX - Operating instructions for Manual Motor Starters MS132 for potentially explosive areas |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS132-32.0 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS132 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 86.55 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | (230 V AC) 30 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (230 V AC) 50 kA |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 480 A |
| Setting Range | 25–32 A |
| Rated Operational Power AC-3 (P e ) | 15 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | 15 kW at 400 V, three-phase |
| Rated Operational Voltage | 690 V AC, main circuit |
| Rated Operational Current (I e ) | 32 A |
| Rated Operational Current AC-3 (I e ) | 32 A |
| Rated Operational Current AC-3e (I e ) | 32 A |
| Rated Operational Current DC-5 (I e ) | 32 A |
| Rated Frequency (f) | 50/60 Hz, main circuit |
| Operating Frequency (f sw ) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.9 ... 3.1 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 32 A |
| Degree of Protection | IP20, housing |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting | 35 mm DIN rail, TH35-7.5 or TH35-15 |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What is the overload current setting range for ABB 1SAM350000R1015?
The MS132-32 has an adjustable overload setting range of 25–32 A and a rated operational current of 32 A. Check the motor nameplate current and the complete protection design before selection.
Can the MS132-32 be used for a 15 kW motor at 400 V?
Its published three-phase AC-3 operational power is 15 kW at 400 V. Check the motor nameplate current against the 25–32 A setting range and verify the installation’s short-circuit and coordination requirements.
What protection and switching functions does the MS132-32 provide?
It combines manual motor switching with thermal overload and magnetic short-circuit protection. It is listed as phase-loss sensitive and has a lockable rotary handle with ON/OFF/TRIP indication.
How is the ABB MS132-32 mounted and connected?
The breaker mounts on a 35 mm DIN rail and uses screw terminals. Its listed body dimensions are 45 mm wide, 97.8 mm high and 86.55 mm deep; check the available panel space and wiring requirements.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.