Technical illustration — ABB 1SAM360000R1011 — 1SAM360000R1011 — Motor protection circuit-breaker

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAM360000R1011 — Motor protection circuit-breaker

relay

Part number: 1SAM360000R1011

ABB 1SAM360000R1011 is the MO132-16 magnetic-only manual motor starter, rated at 16 A. The three-pole device provides manual switching and short-circuit protection and has a lockable rotary handle. A suitable separate thermal or electronic overload relay is required for motor overload protection.

Looking for ABB 1SAM360000R1011? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAM360000R1011
CategoryElectrical & controls
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.55 mm
Product Net Weight0.31 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )200 A
Rated Operational Power AC-3 (P e )7.5 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 7.5 kW
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )16 A
Rated Operational Current AC-3 (I e )16 A
Rated Operational Current AC-3e (I e )16 A
Rated Frequency (f)Main circuit: 50 / 60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Loss1.9 W per pole at rated operating conditions
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 16 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Tightening TorqueMain Circuit 1.5 N·m
Wire Stripping LengthMain Circuit 10 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Mounting on DIN RailTH35-7.5 or TH35-15, 35 mm rail

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Does the ABB MO132-16 provide motor overload protection?

No. This is a magnetic-only starter for short-circuit protection. Motor overload protection requires an appropriate separate thermal or electronic overload relay.

What current and motor power are specified for 1SAM360000R1011?

The MO132-16 has a 16 A rated operational current and a 7.5 kW three-phase AC-3 rating at 400 V. Motor selection also depends on the nameplate current and the complete protection arrangement.

Can the MO132-16 be used on a single-phase supply?

The product is described as suitable for single-phase and three-phase applications. Confirm the wiring, motor data and complete protection arrangement for the intended installation before ordering.

How is the MO132-16 mounted and connected?

It is a three-pole unit with screw terminals and DIN-rail mounting. Its published dimensions are 45 mm wide, 97.8 mm high and 86.55 mm deep.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.