Technical illustration — ABB 1SAM461000R1014 — 1SAM461000R1014 — Motor protection circuit-breaker

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAM461000R1014 — Motor protection circuit-breaker

relay

Part number: 1SAM461000R1014

ABB MO165-32, part 1SAM461000R1014, is a 3-pole magnetic-only manual motor starter rated 32 A. It provides manual switching and short-circuit protection and has screw terminals and a rotary handle. Its AC-3 motor power rating is 15 kW at 400 V, three-phase. A suitable separate thermal or electronic overload relay is required for motor overload protection.

Looking for ABB 1SAM461000R1014? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAM461000R1014
CategoryElectrical & controls
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter Magnetic Only MO165-16 ... MO165-65
Cut-off Current CharacteristicCut-off Current Characteristic @ 400/690V -Manual Motor Starter MS165/MO165
Product Net Width55 mm
Product Net Height142.65 mm
Product Net Depth / Length122.1 mm
Product Net Weight0.97 kg
Rated Service Short-Circuit Breaking Capacity (I cs )100 kA at 230 V AC; 100 kA at 400 V AC; 50 kA at 440 V AC; 30 kA at 500 V AC; 10 kA at 690 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )480 A
Rated Operational Power AC-3 (P e )15 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 15 kW
Rated Operational VoltageMain circuit: 690 V AC; 250 V DC
Rated Operational Current (I e )32 A
Rated Operational Current AC-3 (I e )32 A
Rated Operational Current AC-3e (I e )32 A
Rated Operational Current DC-5 (I e )32 A
Rated Frequency (f)Main circuit: 50 / 60 Hz
Operating Frequency (f sw )0 ... 415 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 8 kV
Rated Insulation Voltage (U i )1000 V
Power Loss4.4 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 32 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 1 ... 35 mm²
Tightening TorqueMain Circuit 4 N·m
Wire Stripping LengthMain Circuit 16 mm
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Protection typeMagnetic-only short-circuit protection; separate overload relay required for motor overload protection.
Actuator typeRotary handle with ON / OFF / TRIP indication

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Does the ABB MO165-32 provide motor overload protection?

No. This is a magnetic-only starter for short-circuit protection. An appropriately selected thermal or electronic overload relay is required for motor overload protection.

What are the current and motor power ratings of 1SAM461000R1014?

The MO165-32 is rated at 32 A operational current and 15 kW for a three-phase motor at 400 V under AC-3 duty. Check motor nameplate current and the complete installation before selection.

What is the MO165-32 short-circuit breaking capacity?

Its rated service breaking capacity Ics is 100 kA at 400 V AC and 10 kA at 690 V AC. The applicable rating depends on voltage and the installation; verify fault level and coordination.

What are the dimensions and terminal type of the MO165-32?

The unit measures 55 mm wide, 142.65 mm high and 122.1 mm deep, and has screw terminals. Check available panel space and mounting clearances before ordering.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.