1SAM461000R1015 — MO165-42 Circuit breaker for magnetic only protection 42A MO16542

relay

Part number: 1SAM461000R1015

ABB MO165-42 (1SAM461000R1015) is a 42 A magnetic-only manual motor starter for manual switching and short-circuit protection. It has a rotary handle and a disconnect function. Motor overload protection requires an appropriate separate thermal or electronic overload relay.

Looking for ABB 1SAM461000R1015? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAM461000R1015
CategoryElectrical & controls
Published component descriptionMO165-42 Circuit breaker for magnetic only protection 42A MO16542
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Protection typeMagnetic short-circuit protection; separate overload relay required for motor overload protection
Rated operational current42 A
Rated service short-circuit breaking capacity Ics50 kA at 400 V AC
Rated instantaneous short-circuit current setting Ii630 A
Rated operational power22 kW at 400 V AC, AC-3 / AC-3e
Number of poles3
Main circuit connectionsScrew terminals
Dimensions (width × height × depth)55 × 142.65 × 122.1 mm
Net weight0.97 kg
ActuatorRotary handle

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Does the MO165-42 provide motor overload protection?

No. It provides magnetic short-circuit protection, not standalone motor overload protection. ABB specifies an appropriate thermal or electronic overload relay for motor overload protection.

What are the current and short-circuit ratings of the ABB MO165-42?

The rated operational current is 42 A. Its rated service short-circuit breaking capacity Ics is 50 kA at 400 V AC, and its rated instantaneous short-circuit setting is 630 A. Check the prospective fault current and circuit conditions before selection.

Can the MO165-42 be used with a 22 kW motor?

ABB lists a rated operational power of 22 kW at 400 V for AC-3 and AC-3e. This rating alone does not establish suitability: check the motor nameplate current, supply, fault level and required overload protection.

What are the dimensions and connection type of the MO165-42?

The unit measures 55 mm wide, 142.65 mm high and 122.1 mm deep. It has three poles and screw connections. Check available panel space and the existing equipment details before ordering.