Technical illustration — ABB 1SAX531001R1101 — 1SAX531001R1101 — Electronic overload relay

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAX531001R1101 — Electronic overload relay

relay

Part number: 1SAX531001R1101

ABB EF205-210 (1SAX531001R1101) is a self-supplied electronic motor overload relay with a 63–210 A adjustable current range. It provides overload and phase-failure protection, selectable trip classes 10E, 20E and 30E, and manual or automatic reset. It includes one normally closed trip contact, one normally open signal contact, and stop, test and trip indication functions.

Looking for ABB 1SAX531001R1101? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAX531001R1101
CategoryElectrical & controls
Ex Operating InstructionsATEX - Operating instructions for EF electronic overload relay for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Electronic overload relay EF19, EF45, EF65, EF96, EF146, EF205, EF370, EF460, EF750 from cold state
Product Net Width105 mm
Product Net Height171 mm
Product Net Depth / Length122.8 mm
Product Net Weight1.256 kg
Setting Range63–210 A
Rated Operational VoltageMain circuit: 1000 V AC; auxiliary circuit: 600 V AC/DC
Rated Operational Current (I e )210 A
Rated Frequency (f)Main circuit: 50/60 Hz; auxiliary circuit: DC or 50/60 Hz
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV
Rated Insulation Voltage (U i )1000 V
Number of Poles3
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (I th )Auxiliary Circuit NC 5 A
Rated Operational Current AC-15 (I e )(240 V) NC 3 A
Rated Operational Current DC-13 (I e )(125 V) NC 0.55 A
Degree of ProtectionHousing IP20; main circuit terminals IP00
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Main CircuitHole Diameter > 8 mm²
Tightening TorqueAuxiliary Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm
Mounting Position1 ... 6
Power Lossat Rated Operating Conditions per Pole 0.107 ... 1.191 W
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600
Published component typeElectronic overload relay
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10E, 20E or 30E, selectable
ResetManual or automatic, selectable
Ambient Operating Temperature−25 to +70 °C, temperature compensated

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What current range does the ABB EF205-210 overload relay cover?

The EF205-210, part number 1SAX531001R1101, has an adjustable overload current setting range of 63–210 A. Check the motor nameplate current and application requirements before selecting it.

Does the EF205-210 need a separate power supply?

No. The EF205-210 is self-supplied and does not require an additional external supply for the relay.

Which trip classes and reset options does the EF205-210 provide?

Trip classes 10E, 20E and 30E are selectable. The relay also offers selectable manual or automatic reset, plus stop, test and trip indication functions.

What motor faults does the EF205-210 protect against?

It provides motor protection against overload and phase failure. Its overload function should not be treated as a substitute for properly coordinated short-circuit protection.

What auxiliary contacts are included on the EF205-210?

It has one normally closed trip contact and one normally open signalling contact. Confirm that the contact ratings suit the control circuit.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part