Catalogue reference. Availability, exact specification and OEM or aftermarket supply are confirmed in your quotation.
1SAZ411201R2002 — Thermal overload relay
relayPart number: 1SAZ411201R2002
ABB TA110DU-110M, part 1SAZ411201R2002, is a three-pole thermal overload relay for motor protection. It has an adjustable 80–110 A setting range, trip class 10A, and one normally open and one normally closed auxiliary contact. Check the motor and contactor details before selecting the relay.
Looking for ABB 1SAZ411201R2002? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAZ411201R2002 |
| Category | Electrical & controls |
| Product Net Width | 80 mm |
| Product Net Height | 120 mm |
| Product Net Depth / Length | 102 mm |
| Product Net Weight | 0.755 kg |
| Setting Range | 80–110 A |
| Rated Operational Voltage | Auxiliary Circuit 440 V DC |
| Rated Operational Current (I e ) | 110 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 5 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.25 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible 1x 16 ... 35 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.3 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Power Loss | at Rated Operating Conditions per Pole 2.5 ... 4.7 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 6-2/0 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-14 AWG |
| Tightening Torque UL/CSA | Auxiliary Circuit 12 in·lb |
| Ambient Air Temperature | Operation: −25 to +55 °C |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10A |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What is the current setting range and trip class of ABB 1SAZ411201R2002?
The TA110DU-110M has an adjustable current setting range of 80–110 A and a trip class of 10A. Check the motor nameplate current and the protection requirements before selecting it.
What protection and auxiliary contacts does the TA110DU-110M provide?
This three-pole thermal overload relay is described as providing motor overload and phase-failure protection. It has one normally open and one normally closed auxiliary contact, plus test and stop functions.
Can the TA110DU-110M be used with my existing motor starter?
The 80–110 A setting range alone does not establish compatibility with a particular starter. Provide the contactor and motor nameplate details, and the equipment model and serial number where available, so the mounting and protection requirements can be checked.
Researched on: