Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SAZ421201R1003 — Thermal overload relay
relayPart number: 1SAZ421201R1003
ABB 1SAZ421201R1003 is the TA200DU-135 three-pole thermal overload relay, with a 100–135 A adjustable current range and trip class 10A. It provides motor overload and phase-failure protection, with temperature compensation, selectable manual or automatic reset, trip indication, STOP and TEST functions, and one normally closed and one normally open auxiliary contact.
Looking for ABB 1SAZ421201R1003? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAZ421201R1003 |
| Category | Electrical & controls |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay TA200DU-135, TA200DU-135 V1000 |
| Product Net Width | 104 mm |
| Product Net Height | 151 mm |
| Product Net Depth / Length | 126 mm |
| Product Net Weight | 0.76 kg |
| Setting Range | 100 ... 135 A |
| Rated Operational Voltage | Main circuit: 690 V AC; auxiliary circuit: 500 V AC or 440 V DC |
| Rated Operational Current (I e ) | 135 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 5 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.25 A |
| Degree of Protection | Housing: IP20; main circuit terminals: IP00 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Hole Diameter > 10 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.3 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 3.3 ... 6.0 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1x 4-0000 AWG |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10A |
| Reset Method | Selectable manual or automatic |
| Ambient Air Temperature | Operation: −25 to +55 °C; storage: −40 to +70 °C |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What current range and trip class does ABB 1SAZ421201R1003 have?
The TA200DU-135 has an adjustable current setting range of 100–135 A and a trip class of 10A. Check the motor current and starting requirements when selecting an overload relay.
What does the TA200DU-135 protect against, and how is it reset?
It is a thermal overload relay for motor protection against overload and phase failure. It has selectable manual or automatic reset, a trip indication, and STOP and TEST functions.
Can the TA200DU-135 be mounted separately from a contactor?
The relay connects directly to suitable block contactors; a separate single-mounting kit is also available as an accessory. Confirm the mounting arrangement and contactor model before ordering.
What auxiliary contacts and voltage ratings does the TA200DU-135 have?
It has one normally closed trip contact and one normally open signal contact. The listed operational voltage is 690 V AC for the main circuit and 500 V AC or 440 V DC for the auxiliary circuit; contact current ratings depend on the switching duty.
Researched on: