Technical illustration — ABB 1SAZ711201R1033 — 1SAZ711201R1033 — Thermal overload relay

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAZ711201R1033 — Thermal overload relay

relay

Part number: 1SAZ711201R1033

ABB 1SAZ711201R1033 (T16-3.1) is a thermal overload relay with an adjustable 2.3–3.1 A setting and class 10 trip characteristic. It provides motor overload and phase-failure protection, selectable manual or automatic reset, trip indication and normally open and normally closed auxiliary contacts.

Looking for ABB 1SAZ711201R1033? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAZ711201R1033
CategoryElectrical & controls
Time-Current Characteristic CurveTripping characteristic - Thermal overload relay T16-3.1
Product Net Width45 mm
Product Net Height76.7 mm
Product Net Depth / Length53.5 mm
Product Net Weight0.1 kg
Setting Range2.3–3.1 A
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC
Rated Operational Current (I e )3.1 A
Rated Frequency (f)Auxiliary Circuit 50 Hz
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (I th )Auxiliary Circuit NC 6 A
Rated Operational Current AC-15 (I e )(120 V) NC 3 A
Rated Operational Current DC-13 (I e )(125 V) NC 0.55 A
Degree of ProtectionIP20
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 4 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm
Power Lossat Rated Operating Conditions per Pole 1.1 ... 2.0 W
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 18-12 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-12 AWG
Published component typeThermal overload relay
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10
Main Circuit ConnectionScrew terminals

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What is the current setting range of the ABB T16-3.1?

ABB 1SAZ711201R1033 is the T16-3.1, with an adjustable overload setting range of 2.3–3.1 A and trip class 10. Check the motor nameplate current and application requirements before selecting the relay.

Does the T16-3.1 reset automatically or manually?

Both modes are selectable. The relay also has a trip indicator and a STOP function; choose the reset mode appropriate to the equipment and its safety requirements.

Does the T16-3.1 provide short-circuit protection?

No. The thermal overload relay requires separate short-circuit protection. Selection must take the complete motor circuit, fault level and applicable coordination requirements into account.

Can the T16-3.1 be mounted independently of a contactor?

The relay is intended for direct attachment to compatible contactors; a separate single-mounting kit is available as an accessory. Confirm the contactor model, motor details and equipment serial number before ordering for a specific installation.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.