Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SAZ711201R1043 — Thermal overload relay
relayPart number: 1SAZ711201R1043
ABB 1SAZ711201R1043 is a T16-10 thermal overload relay for motor overload and phase-failure protection. It has a 7.6–10 A adjustable current range, trip class 10, three protected poles and one normally closed and one normally open auxiliary contact. Manual or automatic reset can be selected.
Looking for ABB 1SAZ711201R1043? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SAZ711201R1043 |
| Category | Electrical & controls |
| Time-Current Characteristic Curve | Tripping characteristic - Thermal overload relay T16-10 |
| Product Net Width | 45 mm |
| Product Net Height | 76.7 mm |
| Product Net Depth / Length | 53.5 mm |
| Product Net Weight | 0.104 kg |
| Setting Range | 7.6–10 A |
| Rated Operational Voltage | Main circuit 690 V AC; auxiliary circuit 600 V AC/DC |
| Rated Operational Current (I e ) | 10 A |
| Rated Frequency (f) | Main circuit 50/60 Hz; auxiliary circuit 50/60 Hz and DC |
| Rated Impulse Withstand Voltage (U imp ) | Auxiliary Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Auxiliary Circuit NC 6 A |
| Rated Operational Current AC-15 (I e ) | (120 V) NC 3 A |
| Rated Operational Current DC-13 (I e ) | (125 V) NC 0.55 A |
| Degree of Protection | IP20 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 4 mm² |
| Tightening Torque | Auxiliary Circuit 1 ... 1.2 N·m |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Power Loss | at Rated Operating Conditions per Pole 1.1 ... 2.0 W |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 18-12 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-12 AWG |
| Published component type | Thermal overload relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip Class | 10 |
| Reset Mode | Selectable manual or automatic |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What current range and trip class does ABB 1SAZ711201R1043 have?
The T16-10 has an adjustable overload current setting of 7.6–10 A and trip class 10. Check the motor nameplate current and starting conditions when selecting a relay.
What protection does the T16-10 provide, and does it replace short-circuit protection?
The relay provides motor overload and phase-failure protection. It is an overload relay, not a substitute for correctly selected short-circuit protection; verify the protective device and coordination for the installation.
Which contactors can the T16-10 mount on?
Published suitable contactors include ABB B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7, AS09, AS12 and AS16. A separate single-mounting kit is also available. Confirm the exact contactor and equipment details before ordering.
Does the T16-10 have manual reset and auxiliary contacts?
Yes. Manual or automatic reset is selectable. The relay has one normally closed trip contact and one normally open signal contact, plus a trip indication and STOP function.
Researched on: