Technical illustration — ABB 1SAZ721201R1028 — 1SAZ721201R1028 — Thermal overload relay

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SAZ721201R1028 — Thermal overload relay

relay

Part number: 1SAZ721201R1028

ABB 1SAZ721201R1028 (TF42-1.7) is a thermal overload relay with an adjustable 1.3–1.7 A setting range and trip class 10. It provides motor overload and phase-failure protection, with selectable manual or automatic reset and one normally open and one normally closed auxiliary contact.

Looking for ABB 1SAZ721201R1028? This catalogue reference is listed under relay. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SAZ721201R1028
CategoryElectrical & controls
Ex Operating InstructionsATEX - Operating instructions for thermal overload relay TF42 for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Thermal overload relay TF42-1.7
Product Net Width45 mm
Product Net Height88.3 mm
Product Net Depth / Length70.5 mm
Product Net Weight0.13 kg
Setting Range1.3–1.7 A
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC
Rated Operational Current (I e )1.7 A
Rated Frequency (f)Auxiliary Circuit 50 Hz
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (I th )Auxiliary Circuit NC 6 A
Rated Operational Current AC-15 (I e )(120 V) NC 3 A
Rated Operational Current DC-13 (I e )(125 V) NC 0.55 A
Degree of ProtectionIP20
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 4 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm
Power Lossat Rated Operating Conditions per Pole 1.1 ... 2.0 W
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 18-10 AWG
Published component typeThermal overload relay
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip class10
Reset methodSelectable manual or automatic
Main circuit connectionScrew terminals

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What current range does ABB 1SAZ721201R1028 cover?

The TF42-1.7 has an adjustable overload setting range of 1.3–1.7 A. Check the motor nameplate current and the application requirements before selecting the relay.

Which contactors can the TF42-1.7 mount on?

The TF42-1.7 is listed for ABB AF09–AF38 contactors. Confirm the complete contactor model and, where relevant, equipment serial number before ordering; a separate mounting kit is needed for standalone mounting.

What protection and trip class does the TF42-1.7 provide?

This thermal overload relay provides motor overload and phase-failure protection with trip class 10. Check the complete motor-starter design for the required short-circuit protection.

Does the TF42-1.7 have manual or automatic reset and auxiliary contacts?

It offers selectable manual or automatic reset and has one normally closed trip contact and one normally open signal contact.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.