Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SBE111111R0102 — Installation Contactor
contactorPart number: 1SBE111111R0102
ABB ESB16-02N-01 installation contactor, part number 1SBE111111R0102, with two normally closed main contacts and a 24 V AC/DC control coil. The two-pole unit is rated 16 A for AC-1 duty and occupies one modular spacing. Confirm the load and circuit requirements before selection.
Looking for ABB 1SBE111111R0102? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SBE111111R0102 |
| Category | Electrical & controls |
| Product Net Width | 18 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.14 kg |
| Number of Main Contacts NO | 0 |
| Number of Main Contacts NC | 2 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit DC |
| Rated Operational Current AC-1 (I e ) | (NC) 16 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Current AC-7a (I e ) | (NC) 16 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 3.7 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 3.7 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 400 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 24 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.9 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Width in Number of Modular Spacings | 1 |
| Built-in Depth | 58 mm |
| Degree of Protection | IP20 |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What coil voltage does ABB 1SBE111111R0102 require?
The ESB16-02N-01 has a 24 V AC/DC control coil. Check the control supply separately from the voltage and current of the load being switched.
Are the contacts normally open or normally closed?
This two-pole contactor has two normally closed main contacts and no normally open main contacts. Check that this contact arrangement matches the intended circuit before ordering.
Can the ESB16-02N-01 switch a 16 A load?
It is rated 16 A for AC-1 loads. This is not a universal rating for every load type: check the utilization category, voltage and load characteristics before selecting the contactor.
How much panel space does this contactor need?
The contactor is 18 mm wide, occupies one modular spacing and has a stated built-in depth of 58 mm. Check the available enclosure space and installation requirements.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.