Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SBE111111R0120 — Installation Contactor
contactorPart number: 1SBE111111R0120
ABB 1SBE111111R0120, type ESB16-20N-01, is a two-pole installation contactor with two normally open main contacts and a 24 V AC/DC control coil. It is rated 16 A for AC-1 operation and mounts on a DIN rail. Check the load category and control supply when selecting the contactor.
Looking for ABB 1SBE111111R0120? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SBE111111R0120 |
| Category | Electrical & controls |
| Product Net Width | 18 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.14 kg |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit DC |
| Rated Operational Current AC-1 (I e ) | (NO) 16 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NO 6 A |
| Rated Operational Current AC-7a (I e ) | (NO) 16 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NO 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NO 3.7 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NO 0.9 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NO 3.7 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NO 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 400 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 24 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.9 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Mounting | DIN rail |
| Terminal Type | Screw terminals |
| Degree of Protection | IP20 |
| Ambient operating temperature | -25 to +55 °C |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What coil voltage does ABB 1SBE111111R0120 require?
The ESB16-20N-01 has a 24 V AC/DC control coil. Check the control supply separately from the voltage being switched by the main contacts.
How many contacts does the ESB16-20N-01 have?
This two-pole contactor has two normally open main contacts and no normally closed main contacts.
Is the 16 A rating suitable for every load on this contactor?
No. The 16 A rating is associated with AC-1 use; the required rating depends on the load and operating conditions. Confirm the specific load and control circuit before selection.
How much panel space does the ESB16-20N-01 need?
The contactor is approximately 18 mm wide, 85 mm high and 65 mm deep. It is designed for DIN-rail mounting; check enclosure clearance for the installation.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.