Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SBE111111R0611 — Installation Contactor
contactorPart number: 1SBE111111R0611
ABB ESB16-11N-06 (1SBE111111R0611) is a two-pole installation contactor with one normally open and one normally closed main contact and a 230 V AC/DC control circuit. It is rated 16 A for AC-1 and AC-7a duty. The ESB16..N range is designed for single-phase loads in household and industrial environments and includes integrated coil overvoltage protection.
Looking for ABB 1SBE111111R0611? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SBE111111R0611 |
| Category | Electrical & controls |
| Product Net Width | 18 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.14 kg |
| Number of Main Contacts NO | 1 |
| Number of Main Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit DC |
| Rated Operational Current AC-1 (I e ) | 16 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Current AC-7a (I e ) | 16 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 3.7 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 3.7 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 400 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.9 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Degree of Protection | IP20 |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What control voltage does ABB 1SBE111111R0611 require?
The ESB16-11N-06 has a rated control voltage of 230 V AC or DC. Verify the control supply and complete part number before ordering; other ESB16 versions have different coil voltages.
What main contact configuration does the ESB16-11N-06 have?
It has two main poles: one normally open (NO) and one normally closed (NC). Check the contact arrangement against the circuit before selecting a replacement.
Can the 1SBE111111R0611 switch a 16 A load?
ABB lists the ESB16 series at 16 A for AC-1 and AC-7a duty. Suitability depends on the load and utilization category; do not assume the 16 A rating applies to every motor or switching duty.
Can an auxiliary contact block be added to this contactor?
ABB lists the EH04-11N and EH04-20N auxiliary contact blocks for the ESB16..N range. Confirm the required auxiliary contact arrangement and panel space before ordering the accessory.
Researched on: