Technical illustration — ABB 1SBE121111R0120 — 1SBE121111R0120 — Installation Contactor

Technical illustration. Published product/series reference; confirm the exact configuration and supplied appearance. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SBE121111R0120 — Installation Contactor

contactor

Part number: 1SBE121111R0120

ABB 1SBE121111R0120 is an ESB20-20N-01 two-pole installation contactor with two normally open main contacts and a 24 V AC/DC control coil. It is rated 20 A for AC-1 and AC-7a duty; its single-phase AC-3 rating is 9 A at 230 V. The unit mounts on a 35 mm DIN rail.

Looking for ABB 1SBE121111R0120? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SBE121111R0120
CategoryElectrical & controls
Product Net Width18 mm
Product Net Depth / Length65 mm
Product Net Height85 mm
Product Net Weight0.14 kg
Number of Main Contacts NO2
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC0
Number of Poles2
Rated Operational VoltageMain Circuit 220 V DC
Rated Frequency (f)Control Circuit DC
Rated Operational Current AC-1 (I e )20 A, normally open contacts
Rated Operational Current AC-3 (I e )9 A at 230 V, single phase
Rated Operational Current AC-7a (I e )20 A, normally open contacts
Rated Operational Current AC-7b (I e )9 A at 230 V, single phase
Rated Operational Power AC-1 (P e )4.6 kW at 230 V, single phase
Rated Operational Power AC-3 (P e )1.3 kW at 230 V, single phase
Rated Operational Power AC-7a (P e )(230 V) Single Phase, NO 4.6 kW
Rated Operational Power AC-7b (P e )(230 V) Single Phase, NO 1.3 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A
Rated Insulation Voltage (U i )400 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (U c )24 V AC/DC
Power Lossat Rated Operating Conditions AC-1 per Pole 1.4 W
Published component typeInstallation Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Mounting35 mm DIN rail

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What coil voltage does ABB 1SBE121111R0120 require?

The ESB20-20N-01 has a 24 V AC/DC control coil. The control voltage is separate from the voltage and current ratings of the switched load.

How many contacts does the ESB20-20N-01 have?

It is a two-pole installation contactor with two normally open main contacts and no normally closed main contacts.

Can this 20 A contactor switch a single-phase motor?

For AC-3 duty, the listed rating is 9 A and 1.3 kW at 230 V single phase. The 20 A rating is for AC-1 or AC-7a duty, not a universal motor rating. Check the motor and operating conditions before selection.

How much panel space does the ESB20-20N-01 need and how is it mounted?

The contactor is 18 mm wide, 85 mm high and 65 mm deep. It is designed for 35 mm DIN rail mounting; check available enclosure space before ordering.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.