Technical illustration. Published product/series reference; confirm the exact configuration and supplied appearance. Images are for reference only. The supplied part’s appearance may differ.
1SBE121111R0602 — Installation Contactor
contactorPart number: 1SBE121111R0602
ABB ESB20-02N-06 (1SBE121111R0602) is a two-pole installation contactor with two normally closed main contacts and a 230 V AC/DC control supply. Its NC contacts are rated 20 A for AC-1 and AC-7a duty. It is intended for controlling single loads in household and industrial environments and includes integrated overvoltage protection. Confirm the load category and electrical ratings before selection.
Looking for ABB 1SBE121111R0602? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SBE121111R0602 |
| Category | Electrical & controls |
| Product Net Width | 18 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.14 kg |
| Number of Main Contacts NO | 0 |
| Number of Main Contacts NC | 2 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 2P |
| Rated Operational Voltage | Main circuit: 250 V AC; 220 V DC |
| Rated Frequency (f) | Control circuit: DC, 50 Hz, 60 Hz or 400 Hz; main circuit: DC, 50 Hz or 60 Hz |
| Rated Operational Current AC-1 (I e ) | (NC) 20 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 9 A |
| Rated Operational Current AC-7a (I e ) | (NC) 20 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 9 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 4.6 kW |
| Rated Operational Power AC-3 (P e ) | (230 V) Single Phase, NC 1.3 kW |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 4.6 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 1.3 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 400 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1.4 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Degree of Protection | IP20 |
| Width in Number of Modular Spacings | 1 |
| Ambient Air Temperature | Operation: -25 to +55 °C; storage: -40 to +80 °C |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What control voltage does the ABB ESB20-02N-06 contactor require?
The rated control voltage is 230 V AC/DC. Check the control supply and the marking on the existing device before selecting a replacement; the control voltage is distinct from the main circuit voltage rating.
Are the contacts on 1SBE121111R0602 normally open or normally closed?
This two-pole contactor has two normally closed main contacts and no normally open main contacts. Verify the required contact arrangement before replacing an existing contactor.
Can the ESB20-02N-06 switch a 20 A motor load?
Not on the basis of its 20 A rating alone. Its NC contacts are rated 20 A in AC-1 and AC-7a, but 9 A in AC-3 and AC-7b at 230 V single-phase. Confirm the load, duty and protection requirements before selection.
What main circuit voltage is the ESB20-02N-06 rated for?
The listed main circuit operational voltage is 250 V AC or 220 V DC. The permissible switching current depends on the load and operating conditions, so the voltage rating alone does not establish suitability.
Researched on: