Technical illustration — ABB 1SBH137001R1231 — 1SBH137001R1231 — Block Contactor Relay

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SBH137001R1231 — Block Contactor Relay

contactor

Part number: 1SBH137001R1231

ABB 1SBH137001R1231, type NF31E-12, is a four-pole block contactor relay for switching auxiliary and control circuits. It has three normally open and one normally closed contacts, a 48–130 V AC/DC electronic control circuit, screw terminals and built-in surge suppression.

Looking for ABB 1SBH137001R1231? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SBH137001R1231
CategoryElectrical & controls
Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Product Net Weight0.27 kg
Number of Auxiliary Contacts NO3
Number of Auxiliary Contacts NC1
Number of Poles4P
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I th )acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (I e )6 A at 24–127 V AC; 4 A at 220–240 V AC; 3 A at 400–440 V AC; 2 A at 500 V AC; 2 A at 690 V AC
Rated Operational Current DC-13 (I e )6 A at 24 V DC; 2.8 A at 48 V DC; 1 A at 72 V DC; 0.55 A at 110 V DC; 0.55 A at 125 V DC; 0.27 A at 220 V DC; 0.27 A at 250 V DC; 0.15 A at 400 V DC; 0.13 A at 500 V DC; 0.1 A at 600 V DC
Rated Short-time Withstand Current Low Voltage (I cw )for 0.1 s 140 A
Rated Insulation Voltage (U i )acc. to IEC 60947-5-1 690 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (U c )48–130 V AC, 50/60 Hz; 48–130 V DC
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 Screws Placed Diagonally
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Tightening TorqueAuxiliary Circuit 1.2 N·m
Terminal TypeScrew terminals
Product NameBlock Contactor Relay
Published component typeBlock Contactor Relay
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Ambient Air TemperatureOperation in free air: -40 to +70 °C

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What control voltage does ABB NF31E-12 accept?

The 1SBH137001R1231 has a rated control voltage of 48–130 V AC at 50/60 Hz or 48–130 V DC. Check the available control supply and the complete part number before ordering.

How many contacts does the NF31E-12 have?

It is a four-pole contactor relay with three normally open and one normally closed auxiliary contacts. Its auxiliary contacts are mechanically linked.

What current can this contactor relay switch?

The contact rating depends on voltage and utilization category. For AC-15, it is rated 6 A at 24–127 V AC and 4 A at 220–240 V AC; for DC-13, it is rated 6 A at 24 V DC and 2.8 A at 48 V DC. Check the rating for the actual load.

How is the ABB NF31E-12 mounted and connected?

The relay can be mounted on a DIN rail or panel and uses screw terminals. Its listed dimensions are 45 mm wide, 86 mm high and 77 mm deep. Check available panel clearance before ordering.

Does the NF31E-12 need an external coil surge suppressor?

The relay has built-in surge suppression, so an additional coil surge suppressor is not normally required. Check the control circuit requirements for the installation.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.