Technical illustration — ABB 1SBH137001R1322 — 1SBH137001R1322 — Block Contactor Relay

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SBH137001R1322 — Block Contactor Relay

contactor

Part number: 1SBH137001R1322

ABB 1SBH137001R1322 (NF22E-13) is a four-pole block contactor relay for switching auxiliary and control circuits. It has two normally open and two normally closed mechanically linked contacts, a 100–250 V AC 50/60 Hz or DC control circuit, built-in surge suppression and screw terminals.

Looking for ABB 1SBH137001R1322? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SBH137001R1322
CategoryElectrical & controls
Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Product Net Weight0.27 kg
Number of Auxiliary Contacts NO2
Number of Auxiliary Contacts NC2
Number of Poles4P
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I th )acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (I e )6 A at 24–127 V; 4 A at 220–240 V; 3 A at 400–440 V; 2 A at 500 V and 690 V
Rated Operational Current DC-13 (I e )6 A / 144 W at 24 V; 2.8 A / 134 W at 48 V; 1 A / 72 W at 72 V; 0.55 A / 60 W at 110 V; 0.55 A / 69 W at 125 V; 0.27 A / 60 W at 220 V; 0.27 A / 68 W at 250 V; 0.15 A / 60 W at 400 V; 0.13 A / 65 W at 500 V; 0.1 A / 60 W at 600 V
Rated Short-time Withstand Current Low Voltage (I cw )for 0.1 s 140 A
Rated Insulation Voltage (U i )acc. to IEC 60947-5-1 690 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching FrequencyAC-15: 1200 cycles per hour; DC-13: 900 cycles per hour
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (U c )100–250 V AC, 50/60 Hz; 100–250 V DC
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Mounting on DIN RailTH35-7.5 and TH35-15, 35 mm rail, IEC 60715
Mounting by Screws (not supplied)2 x M4 Screws Placed Diagonally
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Degree of ProtectionIP20 at auxiliary and coil terminals, IEC 60529
Tightening TorqueAuxiliary Circuit 1.2 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor Relay
Published component typeBlock Contactor Relay
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Ambient operating temperature−40 to +70 °C in free air

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What control voltage does ABB 1SBH137001R1322 require?

The NF22E-13 control circuit is rated for 100–250 V AC at 50 or 60 Hz, or 100–250 V DC. Check the actual control supply and the existing relay label before ordering.

How many contacts does the NF22E-13 have?

It is a four-pole contactor relay with two normally open and two normally closed auxiliary contacts. The contacts are mechanically linked.

What load current can the 1SBH137001R1322 switch?

The operational current depends on voltage and utilization category: AC-15 is 4 A at 220–240 V and 3 A at 400–440 V; DC-13 is 6 A at 24 V. Select against the actual load and duty, not a single universal current rating.

How is the NF22E-13 mounted and connected?

It mounts on TH35-7.5 or TH35-15 DIN rail, or with two diagonally placed M4 screws, which are not supplied. It has screw terminals; its net dimensions are 45 mm wide, 86 mm high and 77 mm deep.

Does the NF22E-13 require an additional coil surge suppressor?

The relay has built-in surge suppression. Confirm the control circuit requirements for the particular installation before selecting any additional protective devices.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part