Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SBH137001R1322 — Block Contactor Relay
contactorPart number: 1SBH137001R1322
ABB 1SBH137001R1322 (NF22E-13) is a four-pole block contactor relay for switching auxiliary and control circuits. It has two normally open and two normally closed mechanically linked contacts, a 100–250 V AC 50/60 Hz or DC control circuit, built-in surge suppression and screw terminals.
Looking for ABB 1SBH137001R1322? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SBH137001R1322 |
| Category | Electrical & controls |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.27 kg |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 4P |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (I th ) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-15 (I e ) | 6 A at 24–127 V; 4 A at 220–240 V; 3 A at 400–440 V; 2 A at 500 V and 690 V |
| Rated Operational Current DC-13 (I e ) | 6 A / 144 W at 24 V; 2.8 A / 134 W at 48 V; 1 A / 72 W at 72 V; 0.55 A / 60 W at 110 V; 0.55 A / 69 W at 125 V; 0.27 A / 60 W at 220 V; 0.27 A / 68 W at 250 V; 0.15 A / 60 W at 400 V; 0.13 A / 65 W at 500 V; 0.1 A / 60 W at 600 V |
| Rated Short-time Withstand Current Low Voltage (I cw ) | for 0.1 s 140 A |
| Rated Insulation Voltage (U i ) | acc. to IEC 60947-5-1 690 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | AC-15: 1200 cycles per hour; DC-13: 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (U c ) | 100–250 V AC, 50/60 Hz; 100–250 V DC |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Mounting on DIN Rail | TH35-7.5 and TH35-15, 35 mm rail, IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Degree of Protection | IP20 at auxiliary and coil terminals, IEC 60529 |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor Relay |
| Published component type | Block Contactor Relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Ambient operating temperature | −40 to +70 °C in free air |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What control voltage does ABB 1SBH137001R1322 require?
The NF22E-13 control circuit is rated for 100–250 V AC at 50 or 60 Hz, or 100–250 V DC. Check the actual control supply and the existing relay label before ordering.
How many contacts does the NF22E-13 have?
It is a four-pole contactor relay with two normally open and two normally closed auxiliary contacts. The contacts are mechanically linked.
What load current can the 1SBH137001R1322 switch?
The operational current depends on voltage and utilization category: AC-15 is 4 A at 220–240 V and 3 A at 400–440 V; DC-13 is 6 A at 24 V. Select against the actual load and duty, not a single universal current rating.
How is the NF22E-13 mounted and connected?
It mounts on TH35-7.5 or TH35-15 DIN rail, or with two diagonally placed M4 screws, which are not supplied. It has screw terminals; its net dimensions are 45 mm wide, 86 mm high and 77 mm deep.
Does the NF22E-13 require an additional coil surge suppressor?
The relay has built-in surge suppression. Confirm the control circuit requirements for the particular installation before selecting any additional protective devices.
Researched on:
Research information may be outdated. Confirm fitment and specifications with our team before ordering.