Technical illustration — ABB 1SBH137001R1331 — 1SBH137001R1331 — Block Contactor Relay

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SBH137001R1331 — Block Contactor Relay

contactor

Part number: 1SBH137001R1331

ABB 1SBH137001R1331, type NF31E-13, is a four-pole block contactor relay for switching auxiliary and control circuits. It has three normally open and one normally closed mechanically linked contacts, screw terminals, a 100–250 V AC 50/60 Hz or DC control coil, and built-in surge protection. Confirm control voltage, contact ratings and mounting requirements for the intended circuit.

Looking for ABB 1SBH137001R1331? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SBH137001R1331
CategoryElectrical & controls
Product Net Width45 mm
Product Net Depth / Length77 mm
Product Net Height86 mm
Product Net Weight0.27 kg
Number of Auxiliary Contacts NO3
Number of Auxiliary Contacts NC1
Number of Poles4P
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I th )acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (I e )6 A at 24–127 V; 4 A at 220–240 V; 3 A at 400–440 V; 2 A at 500 V or 690 V
Rated Operational Current DC-13 (I e )(24 V) 6 A / 144 W
Rated Short-time Withstand Current Low Voltage (I cw )for 0.1 s 140 A
Rated Insulation Voltage (U i )acc. to IEC 60947-5-1 690 V
Rated Impulse Withstand Voltage (U imp )6 kV
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (U c )100–250 V AC, 50/60 Hz; 100–250 V DC
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms
Mounting on DIN RailTH35-15 or TH35-7.5, according to IEC 60715
Mounting by Screws (not supplied)2 x M4 Screws Placed Diagonally
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm
Degree of ProtectionIP20 at auxiliary and coil terminals
Tightening TorqueAuxiliary Circuit 1.2 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor Relay
Published component typeBlock Contactor Relay
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Operating Ambient Temperature−40 to +70 °C
Surge ProtectionBuilt-in

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What coil voltage does ABB 1SBH137001R1331 require?

The NF31E-13 control coil is rated for 100–250 V AC at 50 or 60 Hz, or 100–250 V DC. This is the control supply range, not the switched contact current rating. Check the existing device and control supply before selecting a replacement.

How many normally open and normally closed contacts does the NF31E-13 have?

It has four auxiliary poles: three normally open (NO) and one normally closed (NC). The contacts are mechanically linked. Confirm the required contact arrangement before replacing an existing relay.

What load can the NF31E-13 relay switch?

The rating depends on voltage and utilization category: AC-15 is 4 A at 220–240 V and 3 A at 400–440 V; DC-13 is 6 A at 24 V. The 16 A free-air thermal current at 40 °C is not a universal switching rating. Check the actual load and its applicable rating before selection.

How is the ABB NF31E-13 mounted and connected?

The relay has screw terminals and can be mounted on TH35-15 or TH35-7.5 DIN rail, or with two diagonally placed M4 screws. Its body dimensions are 45 mm wide, 77 mm deep and 86 mm high; check available panel space and the existing mounting arrangement.

Does the NF31E-13 require a separate coil surge suppressor?

The NF31E-13 has built-in surge protection, so an additional coil suppressor is not normally required. Verify the complete control circuit and any equipment-specific requirements before making a substitution.