Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.
1SBH141001R8422 — N22E 110V 50Hz / 110-120V 60Hz Contactor Relay
contactorPart number: 1SBH141001R8422
ABB 1SBH141001R8422 is an N22E four-pole contactor relay for switching auxiliary and control circuits. It has two normally open and two normally closed contacts, screw terminals, and an AC coil rated 110 V at 50 Hz or 110–120 V at 60 Hz.
Looking for ABB 1SBH141001R8422? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | ABB |
|---|---|
| Part number | 1SBH141001R8422 |
| Category | Electrical & controls |
| Published component description | N22E 110V 50Hz / 110-120V 60Hz Contactor Relay |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Control circuit voltage | 110 V AC at 50 Hz; 110–120 V AC at 60 Hz |
| Auxiliary contact configuration | 2 normally open + 2 normally closed |
| Number of poles | 4 |
| Terminal type | Screw terminals |
| Conventional free-air thermal current | 16 A at 40 °C, according to IEC 60947-5-1 |
| Rated operational current AC-15 | 6 A at 24–127 V; 4 A at 220–240 V; 3 A at 380–440 V; 2 A at 500 V and 690 V |
| Rated insulation voltage | 690 V according to IEC 60947-5-1; 600 V according to UL/CSA |
| Dimensions | 44 mm wide × 74 mm high × 74 mm deep |
| Coil terminal protection | IP20 |
| Maximum mechanical switching frequency | 6,000 cycles per hour |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What coil voltage does ABB 1SBH141001R8422 require?
The AC-operated coil is rated 110 V at 50 Hz or 110–120 V at 60 Hz. Check the control supply voltage and frequency before selecting the relay.
How many contacts does the N22E contactor relay have?
This four-pole relay has two normally open and two normally closed auxiliary contacts (2 NO + 2 NC) for switching control and auxiliary circuits.
Is the 16 A rating the switching current for every load?
No. The 16 A value is the conventional free-air thermal current at 40 °C. The AC-15 operational rating depends on voltage: for example, it is 4 A at 220–240 V. Check the load and utilization category.
Will this relay replace the one in my equipment?
Compatibility cannot be confirmed from the equipment name alone. Compare the full part number, coil voltage and frequency, contact arrangement, terminals and load ratings; provide the equipment model and serial number for verification.
Researched on: