Technical illustration — ABB 1SBL113001R8110 — 1SBL113001R8110 — Block Contactor

Technical illustration. Representative component image; exact configuration and appearance may vary. Images are for reference only. The supplied part’s appearance may differ.

ABB

1SBL113001R8110 — Block Contactor

contactor

Part number: 1SBL113001R8110

ABB 1SBL113001R8110 (ASL12-30-10-81) is a three-pole block contactor for control of three-phase motors and power circuits. It has a 24 V DC coil, three normally open main contacts and one built-in normally open auxiliary contact. The low-consumption coil is suitable for direct PLC output control subject to output ratings.

Looking for ABB 1SBL113001R8110? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerABB
Part number1SBL113001R8110
CategoryElectrical & controls
Product Net Width45 mm
Product Net Depth / Length72.5 mm
Product Net Height68 mm
Product Net Weight0.28 kg
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC0
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I th )acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 25 A
Rated Operational Current AC-1 (I e )(690 V) 40 °C 24 A
Rated Operational Current AC-3 (I e )(415 V) 60 °C 12 A
Rated Operational Current AC-15 (I e )(500 V) NC 2
Rated Operational Current DC-13 (I e )(24 V) 6 A / 144 W
Rated Operational Power AC-3 (P e )(400 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (I cw )at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 124 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 155 A
Rated Insulation Voltage (U i )acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (U c )24 V DC
Power Lossat Rated Operating Conditions AC-1 per Pole 1.2 W
Operate TimeBetween Coil De-energization and NC Contact Closing 15 ... 20 ms
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Published component typeBlock Contactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Terminal TypeScrew terminals on main circuit

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

What coil voltage does ABB 1SBL113001R8110 require?

The ASL12-30-10-81 has a 24 V DC control coil. The coil terminals are polarity-sensitive: A1 is positive and A2 is negative. Do not confuse the coil voltage with the main power-circuit voltage.

How many main and auxiliary contacts does the ASL12-30-10-81 have?

It has three normally open main contacts and one built-in normally open auxiliary contact. The auxiliary contact is separate from the three main poles.

Can the 1SBL113001R8110 contactor be controlled by a PLC?

The low-consumption DC coil is described as suitable for direct PLC output control. Check the particular PLC output and power supply ratings before selecting it for a control circuit.

What are the dimensions of the ABB ASL12-30-10-81?

Its listed net dimensions are 45 mm wide, 68 mm high and 72.5 mm deep. The listed net weight is 0.28 kg.

Is the ASL12-30-10-81 suitable for controlling a three-phase motor?

It is intended for three-phase motor control, but suitability depends on the motor and switching duty. Confirm the motor voltage, current, duty and protection requirements; for equipment fitment, provide the model and serial number.

Researched on:

Research information may be outdated. Confirm fitment and specifications with our team before ordering.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.