Honeywell Kromschroder TC 410-10N Valve Proving Control - Tightness Controls Test Period 100-600S
HydraulicsPart number: TC 410-10N
The Kromschroder TC 410-10N is a valve proving control for leakage testing of two gas safety valves before burner start or after shutdown. It uses an external pressure switch and has an adjustable 100–600 second test period. The listed supply is 110/120 V AC, 50/60 Hz. Confirm the equipment and gas-train details before selecting a replacement.
Looking for Kromschroder TC 410-10N? This catalogue reference is listed under Hydraulics. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | Kromschroder |
|---|---|
| Part number | TC 410-10N |
| Category | Hydraulics |
| Published designation | Honeywell Kromschroder TC 410-10N Valve Proving Control - Tightness Controls Test Period 100-600S |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Test period | 100–600 s, adjustable |
| Supply voltage | 110/120 V AC, 50/60 Hz |
| Pressure sensing | External pressure switch required |
| Test timing | Before burner start or after burner shutdown |
| Enclosure protection | IP 40 |
| Ambient temperature | −15 to +60 °C; no condensation |
| Electrical connection | Screw terminals, 2.5 mm² |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
What does the TC 410-10N valve proving control do?
It checks two gas safety shut-off valves for leakage before burner start or after shutdown. A detected unacceptable leak prevents burner start. Its suitability for a particular installation must be confirmed.
What test period does the TC 410-10N use?
The test period is adjustable from 100 to 600 seconds. The appropriate setting depends on the installation, including test volume, inlet pressure and the leakage rate to be detected.
Does the TC 410-10N require a separate pressure switch?
Yes. An external gas pressure switch is required between the two valves being monitored. Gas type and inlet pressure depend on the selected pressure switch. Confirm the switch and installation requirements before ordering.
What supply voltage does the TC 410-10N require, and will it replace my existing control?
The TC 410-10N is listed for 110/120 V AC, 50/60 Hz. Do not assume another TC 410 variant is interchangeable: provide the existing control nameplate, equipment model and serial number, voltage and gas-train details for verification.