GV4AE11 — TeSys GV4 auxiliary contact block, for motor circuit breakers GV4. 1C/O contact, it performs Open/Close OF function or Trip alarm SD function, depending of its location in the…

Cable management & power transfer

Part number: GV4AE11

GV4AE11 — TeSys GV4 auxiliary contact block, for motor circuit breakers GV4. 1C/O contact, it performs Open/Close OF function or Trip alarm SD function, depending of its location in the… — Schneider Electric reference GV4AE11. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Looking for Schneider Electric GV4AE11? This catalogue reference is listed under Cable management & power transfer. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerSchneider Electric
Part numberGV4AE11
CategoryCable management & power transfer
RangeTeSys
Product or Component TypeAuxiliary contact
Range compatibilityTeSys TeSys GV4 TeSys TeSys BV4
[Ue] rated operational voltage<= 690 V
[Ith] conventional free air thermal current5 A IEC 60947-5-1 5 A CSA C22.2 No 14 5 A UL 508
Mounting ModeInternal mounting
[Ui] rated insulation voltage690 V IEC 60947-1
[Ie] rated operational current5 A <= 690 V AC-12 IEC 60947-5-1 5 A <= 48 V AC-15 IEC 60947-5-1 4 A 110/127 V AC-15 IEC 60947-5-1 3 A 220/240 V AC-15 IEC 60947-5-1 2.5 A 380...440 V AC-15 IEC 60947-5-1 0.11 A 660/690 V AC-15 IEC 60947-5-1 5 A <= 24 V DC-12 IEC 60947-5-1 2.5 A 48 V DC-12 IEC 60947-5-1 0.6 A 110/127 V DC-12 IEC 60947-5-1 0.3 A 250 V DC-12 IEC 60947-5-1 2.5 A <= 24 V DC-12 IEC 60947-5-1 1.2 A 48 V DC-12 IEC 60947-5-1 0.35 A 110/127 V DC-12 IEC 60947-5-1 0.05 A 250 V DC-12 IEC 60947-5-1 1 A <= 24 V DC-12 IEC 60947-5-1 0.2 A 48 V DC-12 IEC 60947-5-1 0.05 A 110/127 V DC-12 IEC 60947-5-1 0.03 A 250 V DC-12 IEC 60947-5-1
Rated power in VA120 VA AC-12 24 V IEC 60947-5-1 240 VA AC-12 48 V IEC 60947-5-1 635 VA AC-12 110/127 V IEC 60947-5-1 1200 VA AC-12 230/240 V IEC 60947-5-1 2200 VA AC-12 380/440 V IEC 60947-5-1 3450 VA AC-12 660/690 V IEC 60947-5-1
Rated power in WDC-12 120 W 24 V IEC 60947-5-1 DC-12 120 W 48 V IEC 60947-5-1 DC-12 66 W 110 V IEC 60947-5-1 DC-12 75 W 250 V IEC 60947-5-1
Associated fuse rating5 A gG at 690 V conforming to IEC 60947-5-1
Minimum switching current2 mA
Minimum switching voltage17 V
Connections - terminalsSpring terminals 1 0.0008…0.002 in² (0.5…1.5 mm²) - cable stiffness: flexible without cable end
Wire stripping length0.3 in (8 mm)
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Research is not yet available for this part in English. Ask our team for help.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.