LC1D80AKUE — Contactor

contactor

Part number: LC1D80AKUE

LC1D80AKUE — Contactor — Schneider Electric reference LC1D80AKUE. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Looking for Schneider Electric LC1D80AKUE? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerSchneider Electric
Part numberLC1D80AKUE
CategoryElectrical & controls
RangeTeSys TeSys Deca
Range of ProductTeSys Deca
Product or Component TypeContactor
Poles description3P
[Ue] rated operational voltagePower circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current80 A (at <140 °F (60 °C)) at <= 440 V AC-1 for power circuit 66 A (at <140 °F (60 °C)) at <= 440 V AC-3 for power circuit 66 A (at <140 °F (60 °C)) at <= 440 V AC-3e for power circuit
[Uc] control circuit voltage100...250 V AC 50/60 Hz 100...250 V DC
Motor power kW22 kW at 220...230 V AC 50/60 Hz (AC-3) 37 kW at 380...400 V AC 50/60 Hz (AC-3) 37 kW at 415 V AC 50/60 Hz (AC-3) 37 kW at 440 V AC 50/60 Hz (AC-3) 37 kW at 500 V AC 50/60 Hz (AC-3) 37 kW at 660...690 V AC 50/60 Hz (AC-3) 22 kW at 220...230 V AC 50/60 Hz (AC-3e) 37 kW at 380...400 V AC 50/60 Hz (AC-3e) 37 kW at 415 V AC 50/60 Hz (AC-3e) 37 kW at 440 V AC 50/60 Hz (AC-3e) 37 kW at 500 V AC 50/60 Hz (AC-3e) 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating5 hp at 115 V AC 60 Hz for 1 phase motors 10 hp at 230/240 V AC 60 Hz for 1 phase motors 20 hp at 200/208 V AC 60 Hz for 3 phase motors 20 hp at 230/240 V AC 60 Hz for 3 phase motors 40 hp at 460/480 V AC 60 Hz for 3 phase motors 50 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ith] conventional free air thermal current80 A (at 140 °F (60 °C)) for power circuit 10 A (at 140 °F (60 °C)) for signalling circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 1000 A at 440 V AC for power circuit conforming to IEC 60947
Rated breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current110 A 104 °F (40 °C) - 10 min for power circuit 260 A 104 °F (40 °C) - 1 min for power circuit 640 A 104 °F (40 °C) - 10 s for power circuit 900 A 104 °F (40 °C) - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit
Associated fuse rating125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit 10 A gG for signalling circuit conforming to IEC 60947-5-1
Average impedance1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole9.6 W AC-1 6.3 W AC-3 6.3 W AC-3e
[Ui] rated insulation voltagePower circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-1
Overvoltage categoryIII
[Uimp] rated impulse withstand voltage6 kV IEC 60947
Control circuit voltage limits<= 0.1 Uc (-40…158 °F (-40…70 °C)):drop-out AC/DC 0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC/DC 1...1.1 Uc (140…158 °F (60…70 °C)):operational AC/DC
Inrush power in VA18 VA 50/60 Hz (at 68 °F (20 °C))
Inrush power in W14 W 68 °F (20 °C))
Hold-in power consumption in VA1.8 VA 50/60 Hz (at 68 °F (20 °C))
Hold-in power consumption in W1.2 W 68 °F (20 °C)
Operating time55...65 ms closing 20...80 ms opening
Maximum operating rate3600 cyc/h at 60 °C
Connections - terminalsControl circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid Power circuit: EverLink BTR screw connectors 1 0.002…0.05 in² (1…35
Tightening torqueControl circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.8 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm) Power circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm) Power circuit 44.3 lbf.in (5 N.m) pozidriv No 2 M4 Control circuit 15.05 lbf.in (1.7 N.m) pozidriv No 2 M3.5
Published component typeContactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.