Component reference image: Published product/series reference; confirm the exact configuration and supplied appearance.

Representative component image—not a photograph of this exact brand or part number. Confirm the specification; the supplied part may look different.

Schneider Electric

LC1F800 — Contactor

contactor

Part number: LC1F800

LC1F800 — Contactor — Schneider Electric reference LC1F800. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Looking for Schneider Electric LC1F800? This catalogue reference is listed under contactor. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerSchneider Electric
Part numberLC1F800
CategoryElectrical & controls
RangeTeSys
product nameTeSys F
Product or Component TypeContactor
Poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current1000 A 104 °F (40 °C)) <= 440 V AC AC-1 800 A 131 °F (55 °C)) <= 440 V AC AC-3
Motor power kW450 kW at 1000 V AC 50/60 Hz (AC-3) 450 kW at 500 V AC 50/60 Hz (AC-3) 475 kW at 660...690 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-4) 450 kW at 380...400 V AC 50/60 Hz (AC-3) 450 kW at 415 V AC 50/60 Hz (AC-3) 450 kW at 440 V AC 50/60 Hz (AC-3) 250 kW at 220...240 V AC 50/60 Hz (AC-3)
[Uc] control circuit voltage110...400 V AC 40...400 Hz with LX1/LX9 coil 110...400 V DC with LX4 coil 100...250 V AC 50/60 Hz with LXE coil 100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current1000 A (at 104 °F (40 °C))
Irms rated making capacity8000 A AC conforming to IEC 60947-4-1
Rated breaking capacity6400 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current2600 A 104 °F (40 °C) - 3 min 5500 A 104 °F (40 °C) - 10 s 4600 A 104 °F (40 °C) - 30 s 3600 A 104 °F (40 °C) - 1 min 1700 A 104 °F (40 °C) - 10 min
Associated fuse rating1000 A gG at <= 440 V 800 A aM at <= 440 V
Average impedance0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole120 W AC-1 77 W AC-3
Control circuit voltage limitsOperational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.3...0.5 Uc DC with LX4 coil Operational: 85...275 V AC 50/60 Hz with LXE coil Drop-out: 0...60 V AC 50/60 Hz with LXE coil Operational: 85...418 V DC with LXE coil Drop-out: 0...45 V DC with LXE coil
Operating time60...80 ms closing with LX1/LX9 coil 160...180 ms opening with LX1/LX9 coil 60...80 ms closing with LX4 coil 40...50 ms opening with LX4 coil 40...80 ms closing with LXE coil 6...54 ms opening with LXE coil
Mounting SupportPlate
Connections - terminalsPower circuit bar 2 60 x 5 mm Power circuit bolted connection Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)
Tightening torquePower circuit 513.3 lbf.in (58 N.m) Control circuit 10.6 lbf.in (1.2 N.m)
Inrush power in VA1700 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 1900 VA (at 68 °F (20 °C))with LX4 coil 460…730 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 500…680 VA cos phi 0.5 (at 68 °F (20 °C))with LXE coil
Hold-in power consumption in VA12 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 12 VA (at 68 °F (20 °C))with LX4 coil 7…10 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 4.0…5.5 VA cos phi 0.5 (at 68 °F (20 °C))with LXE coil
Maximum operating rate600 cyc/h 131 °F (55 °C)
Published component typeContactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.

Product questions

Research is not yet available for this part in English. Ask our team for help.

Get a quote for this part

Make yourself at home.

Choose your language and delivery destination. Final pricing and shipping are confirmed in your quote.