Catalogue reference. Availability, exact specification and OEM or aftermarket supply are confirmed in your quotation.
LV430520 — This Micrologic 2.2 M is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 150A rating electronic trip unit is an optimum choice for motor…
Sensors & automationPart number: LV430520
LV430520 — This Micrologic 2.2 M is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 150A rating electronic trip unit is an optimum choice for motor… — Schneider Electric reference LV430520. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Looking for Schneider Electric LV430520? This catalogue reference is listed under Sensors & automation. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | Schneider Electric |
|---|---|
| Part number | LV430520 |
| Category | Sensors & automation |
| Range | ComPact |
| Range of Product | ComPact NSX100...250 |
| Product or Component Type | Trip unit |
| Range Compatibility | ComPact NSX160 ComPact NSX250 |
| Number of poles | 3P |
| Protected poles description | 3t |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 150 A 149 °F (65 °C) |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network Frequency | 50/60 Hz |
| Complementary motor protection | Phase unbalance |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 70...150 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120 s 1.5 x Ir 5 6.5 s 6 x Ir 5 5 s 7.2 x Ir 5 240 s 1.5 x Ir 10 13.5 s 6 x Ir 10 10 s 7.2 x Ir 10 480 s 1.5 x Ir 20 26 s 6 x Ir 20 20 s 7.2 x Ir 20 |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 5...13 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.01 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 2250 A |
| Earth-leakage protection | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.
Product questions
Research is not yet available for this part in English. Ask our team for help.