Representative component image—not a photograph of this exact brand or part number. Confirm the specification; the supplied part may look different.
LV433892 — This Micrologic 4.2 AL is a 4 poles 4d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all…
Cable management & power transferPart number: LV433892
LV433892 — This Micrologic 4.2 AL is a 4 poles 4d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference LV433892. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Looking for Schneider Electric LV433892? This catalogue reference is listed under Cable management & power transfer. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.
Availability on request
Technical specifications
| Manufacturer | Schneider Electric |
|---|---|
| Part number | LV433892 |
| Category | Cable management & power transfer |
| Range | ComPact |
| Range of product | ComPact NSX100...250 |
| Product or component type | Trip unit |
| Range compatibility | ComPact NSX250 |
| Number of poles | 4P |
| Protected poles description | 3t 3t + N/2 4t |
| Trip unit protection functions | LSoI |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rated current | 250 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 100...250 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 3000 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A |
| Earth-leakage protection sensitity adjustment type IÎn | Adjustable |
| [IÎn] earth-leakage protection sensitivity adjustment range | 5 A 300 mA 100 mA 500 mA 30 mA 1 A 3 A |
| Earth-leakage protection specific mode | OFF using the IÎn rotary switch |
| Earth-leakage protection time delay adjustement type Ît | Adjustable |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.