Schneider Electric

XPSMP11123 — Safety controller with pre-defined function

control module

Part number: XPSMP11123

XPSMP11123 — Safety controller with pre-defined function — Schneider Electric reference XPSMP11123. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Looking for Schneider Electric XPSMP11123? This catalogue reference is listed under control module. Send the part number and your equipment details so we can confirm the specification, availability and a quotation including shipping.

Availability on request

Price on quotation

Shipping includedWarranty & serviceGet a quote for this part

Technical specifications

ManufacturerSchneider Electric
Part numberXPSMP11123
CategorySensors & automation
Range of ProductPreventa Safety automation
Product or Component TypeSafety controller with pre-defined function
[Us] Rated Supply Voltage24 V DC - 20...20 %
Connections - terminalsCaptive screw clamp terminals flexible 0.14...0.75 mm² without cable end, 2 wires Captive screw clamp terminals solid 0.14...0.75 mm² without cable end, 2 wires Captive screw clamp terminals flexible 0.14...2.5 mm² without cable end, 1 wire Captive screw clamp terminals solid 0.14...2.5 mm² without cable end, 1 wire Captive screw clamp terminals flexible 0.25...1 mm² with cable end, without bezel, 2 wires Captive screw clamp terminals flexible 0.25...1.5 mm² with cable end, with bezel, 1 wire Captive screw clamp terminals flexible 0.25...2.5 mm² with cable end, without bezel, 1 wire Captive screw clamp terminals flexible 0.5...1.5 mm² with cable end, with double bezel, 2 wires
Synchronisation time between inputs0.5 s 13) 1.5 s 14) 1.5 s 15) 1.5 s 5) 1.5 s 6) 1.5 s 9) Unlimited 3) Unlimited 4) Unlimited 7) Unlimited 8)
Power Consumption in W5 W
Input protection typeInternal, electronic
[Uc] control circuit voltage24 V
Maximum line resistance100 Ohm <6561.7 ft (2000 m)
Breaking capacity20 mA 24 V static output circuit 1.5 A 24 V DC-13)50 ms relay output
Output thermal current2 A for 1 output and 4 A for the other 2 outputs relay 3.3 A for all 3 outputs relay simultaneously 6 A for 1 output and 2 A for the other 2 outputs relay
[Ith] conventional free air thermal current20 A
Associated fuse rating4 A gG relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200 6 A fast blow relay output EN/IEC 60947-5-1, DIN VDE 0660 part 200
Minimum output current10 mA relay output
Minimum output voltage17 V relay output
Maximum response time on input open30 ms
[Ui] rated insulation voltage300 V 2)EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
[Uimp] rated impulse withstand voltage4 kV III EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
Local signalling12 LEDs
Mounting Support35 mm symmetrical DIN rail
Depth4.5 in (114 mm)
Height3.9 in (99 mm)
Width1.8 in (45 mm)
Product Weight0.71 lb(US) (0.32 kg)
Published component typeSafety controller with pre-defined function
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogue information may contain errors or be out of date. Full specifications and verified details are available on request. Confirm the part number and equipment fitment with us before ordering.