Ilustración técnica. Representative component image; exact configuration and appearance may vary. Imágenes solo de referencia. La apariencia de la pieza suministrada puede variar.
1SAE231111R0422 — Installation Contactor
contactorReferencia de la pieza: 1SAE231111R0422
ABB 1SAE231111R0422 is an ESB25-22N-04 four-pole installation contactor with two normally open and two normally closed main contacts. Its control circuit is rated 110–120 V AC/DC, and its AC-1 operational current is 25 A. Verify the control supply, contact arrangement and load ratings for the intended installation.
¿Busca ABB 1SAE231111R0422? Esta referencia de catálogo está clasificada como «contactor». Envíe el número de pieza y los datos de su equipo para confirmar las especificaciones y la disponibilidad y preparar un presupuesto con envío incluido.
Disponibilidad bajo consulta
Especificaciones técnicas
| Fabricante | ABB |
|---|---|
| Referencia de la pieza | 1SAE231111R0422 |
| Categoría | Electricidad y control |
| Product Net Width | 36 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.24 kg |
| Number of Main Contacts NO | 2 |
| Number of Main Contacts NC | 2 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main Circuit 220 V DC |
| Rated Frequency (f) | Control Circuit 400 Hz |
| Rated Operational Current AC-1 (I e ) | 25 A |
| Rated Operational Current AC-3 (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Current AC-7a (I e ) | (NC) 25 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NC 6 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-3 (P e ) | 1.3 kW at 230 V single phase, NO or NC |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 5.8 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NC 0.9 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 72 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 110–120 V AC/DC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
La información del catálogo puede contener errores o estar desactualizada. Las especificaciones completas y los datos verificados están disponibles bajo petición. Confirme con nosotros la referencia y la compatibilidad con su equipo antes de realizar el pedido.
Preguntas sobre el producto
La información investigada sobre esta pieza aún no está disponible en español. Consulte a nuestro equipo.
Obtener un presupuesto para esta pieza